Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 25, 2016, 08:45 AM
  • 08 0146_08 0145_7252016_014749.mp4

Date
07/25/2016
W/O
0574374
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00006
PipeID
P00202
Time
1:45 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0203
Sewer Name
08 FIGUEROA STREET TRUNK
City
COMPTON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
01
Purpose
Routine Assessment
Project
20160723MDM_FIGUEROA_STREET_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
08 0146
Downstream MH
08 0145
Dir. of Survey
Downstream
Length Surveyed
155.3 ft.
Total Length
155.3 ft.
Structural Index
2
Structural Quick
312A
Structural Rating
27
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
27
Pipe schematic from manhole 08 0146 to 08 0145
MH: 08 0146MH: 08 0145downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. OPEN0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:40AM14.8 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SLIGHT14.8 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - HAIRLINE47.3 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SLIGHT72 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H79.9 ft. MGO - General Observation - 12" VCP125 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SLIGHT129.1 ft. FC - Fracture Circumferential, from 07 to 09 o'clock, within 8 inches of joint: YES - H129.1 ft. FC - Fracture Circumferential, from 04 to 05 o'clock, within 8 inches of joint: YES - H132.9 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - SLIGHT137.5 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - SLIGHT137.5 ft. FC - Fracture Circumferential, from 11 to 02 o'clock, within 8 inches of joint: YES - SLIGHT141.5 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H149.5 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H149.5 ft. FC - Fracture Circumferential, from 04 to 05 o'clock, within 8 inches of joint: YES - H155 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. OPEN155.3 ft. AMH - Downstream Manhole, Survey Ends - 2:15AM

Observation photos (1)

  • General Observation - 12" VCP

    79.9 ft. - General Observation - 12" VCP

Observations (20)

DistanceCodeObservation
47.3FCSLIGHT
0MWL
155MGOConn. @ Mh, 9 O' Clock. OPEN
149.5FCH
14.8FCSLIGHT
129.1FCH
149.5FCH
72FCH
0MGOConn. @ Mh, 9 O' Clock. OPEN
0MWM
137.5FCSLIGHT
14.8FLHAIRLINE
137.5FCSLIGHT
141.5FCH
0AMH1:40AM
125FCSLIGHT
155.3AMH2:15AM
129.1FCH
132.9FCSLIGHT
79.9MGO12" VCP

Properties (4)

custom_field_three
SLIGHT FRACTURES
custom_field_two
4
customer
LACSD
datetime
2016-07-25T01:45:11-07:00