Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 23, 2016, 08:17 PM
  • G 0073_G 0096_6232016_132145.mp4

Date
06/23/2016
W/O
0563388
Weather
Dry
Operator/Surveyor
MIRANDA
Sewer ID
Z00347
PipeID
P22101
Time
1:17 PM
Certificate
U-1014-06022542
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7158
Sewer Name
G JOINT OUTFALL G - UNIT 7
City
COMPTON
Loc. details
Parking Lot
Location Code
G
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
20
Purpose
Routine Assessment
Project
20160623AM_JOINT_OUTFALL_G_UNIT_7
Shape
Circular
Upstream MH
G 0073
Downstream MH
G 0096
Dir. of Survey
Downstream
Length Surveyed
2.1 ft.
Total Length
2.1 ft.
Structural Index
4
Structural Quick
5131
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
8
Pipe schematic from manhole G 0073 to G 0096
MH: G 0073MH: G 0096downstream0 ft. AMH - Upstream Manhole, Survey Begins - 1:21 PM0 ft. MWL - Water Level, 50 %of cross sectional area0 ft. MGO - General Observation - PARTIAL STOPLOG IN PLACE, BULKHEADED PIPE/CAPPED CONN. INSIDE THE MH. @ 03 O'CLOCK0 ft. MGO - General Observation - SQUARE PIPE2 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO2 ft. MGO - General Observation - ACTIVE CONN. INSIDE MH. G 96 @ 09 O'CLOCK2.1 ft. AMH - Upstream Manhole, Survey Ends - ABLE TO SEE MH. G 96

Observation photos (8)

  • Upstream Manhole, Survey Begins - 1:21 PM

    0 ft. - Upstream Manhole, Survey Begins - 1:21 PM

  • Water Level, 50 %of cross sectional area

    0 ft. - Water Level, 50 %of cross sectional area

  • General Observation - PARTIAL STOPLOG IN PLACE, BULKHEADED PIPE/CAPPED CONN. INSIDE THE MH. @ 03 O'CLOCK

    0 ft. - General Observation - PARTIAL STOPLOG IN PLACE, BULKHEADED PIPE/CAPPED CONN. INSIDE THE MH. @ 03 O'CLOCK

  • General Observation - SQUARE PIPE

    0 ft. - General Observation - SQUARE PIPE

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO

    2 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO

    2 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: NO

  • General Observation - ACTIVE CONN. INSIDE MH. G 96 @ 09 O'CLOCK

    2 ft. - General Observation - ACTIVE CONN. INSIDE MH. G 96 @ 09 O'CLOCK

  • Upstream Manhole, Survey Ends - ABLE TO SEE MH. G 96

    2.1 ft. - Upstream Manhole, Survey Ends - ABLE TO SEE MH. G 96

Observations (8)

DistanceCodeObservation
2SRV
2.1AMHABLE TO SEE MH. G 96
2SAV
2MGOACTIVE CONN. INSIDE MH. G 96 @ 09 O'CLOCK
0AMH1:21 PM
0MWL
0MGOPARTIAL STOPLOG IN PLACE, BULKHEADED PIPE/CAPPED CONN. INSIDE THE MH. @ 03 O'CLOCK
0MGOSQUARE PIPE

Properties (5)

additional_info
JUST GOING TO HANG THE CAMERA IN THE CENTER OF THE MH. AND ZOOM IN D/S
custom_field_three
REBAR, CORRODED THROUGHOUT
custom_field_two
1
customer
LACSD
datetime
2016-06-23T13:17:02-07:00