Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 22, 2016, 10:59 AM
  • A 0303_A 1226_6222016_043259.mp4

Date
06/22/2016
W/O
0574368
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00325
PipeID
P21654
Time
3:59 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
HO166
Sewer Name
A JOA-1A SAN JOSE CREEK WRP INTERCEPTOR
City
WHITTIER
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
15
Purpose
Capital Improvement Program Assesment
Project
20160621MDM_JOA_1A_SAN_JOSE_CREEK_WRP_INTERCEPTOR
Material
Reinforced Concrete Pipe
Shape
Circular
Height
63 in.
Upstream MH
A 0303
Downstream MH
A 1226
Dir. of Survey
Downstream
Length Surveyed
663.7 ft.
Total Length
663.7 ft.
Structural Index
3
Structural Quick
5641
Structural Rating
72
O&M Index
5
O&M Quick
5141
O&M Rating
9
Overall Index
3
Overall Quick
Overall Rating
81
Pipe schematic from manhole A 0303 to A 1226
MH: A 0303MH: A 1226downstream0 ft. MWM - Water Mark, 70 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:15AM0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG15.1 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG15.1 ft. SAV - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG29.2 ft. SAV - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - SEVER AGG29.2 ft. MGO - General Observation - UNUSAL RUST ON CONCRETE29.2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES - BLISTERING PEELING CONCRETE87.2 ft. MGO - General Observation - MAG COAT 40% START134.1 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES - PEELING CONCRETE231.1 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES - BLISTERING CONCRETE312 ft. SAV - Surface Aggregate Visible, from 09 to 11 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC317.3 ft. MGO - General Observation - MAG COAT 40% FINISH329.2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC329.2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES343.1 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG343.1 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG359.2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG380.3 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE452 ft. MWM - Water Mark, 80 %of cross sectional area452 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG556.8 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE606.6 ft. SAV - Surface Aggregate Visible, from 02 to 03 o'clock, within 8 inches of joint: NO, Start - SEVERE AGG606.6 ft. SAV - Surface Aggregate Visible, from 09 to 10 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG628.4 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES - CIRCUM REBAR628.4 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG628.4 ft. SAV - Surface Aggregate Visible, from 02 to 03 o'clock, within 8 inches of joint: NO, Finish628.4 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR628.4 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish628.4 ft. SAV - Surface Aggregate Visible, from 09 to 10 o'clock, within 8 inches of joint: YES, Finish628.4 ft. MWM - Water Mark, 40 %of cross sectional area633.2 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES, Start - LONG REBAR640.1 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM640.1 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR646.1 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - CIRCUM649.4 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - CIRCUM663.1 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES, Finish - LONG REBAR663.1 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR663.1 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG663.7 ft. AMH - Downstream Manhole, Survey Ends - 5:50AM

Observation photos (26)

  • Water Mark, 70 %of cross sectional area

    0 ft. - Water Mark, 70 %of cross sectional area

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    15.1 ft. - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • General Observation - UNUSAL RUST ON CONCRETE

    29.2 ft. - General Observation - UNUSAL RUST ON CONCRETE

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES - BLISTERING PEELING CONCRETE

    29.2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES - BLISTERING PEELING CONCRETE

  • General Observation - MAG COAT 40% START

    87.2 ft. - General Observation - MAG COAT 40% START

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES - PEELING CONCRETE

    134.1 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES - PEELING CONCRETE

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES - BLISTERING CONCRETE

    231.1 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES - BLISTERING CONCRETE

  • Surface Aggregate Visible, from 09 to 11 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

    312 ft. - Surface Aggregate Visible, from 09 to 11 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

  • General Observation - MAG COAT 40% FINISH

    317.3 ft. - General Observation - MAG COAT 40% FINISH

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

    329.2 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES

    329.2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    343.1 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

    359.2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

    380.3 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

  • Water Mark, 80 %of cross sectional area

    452 ft. - Water Mark, 80 %of cross sectional area

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

    556.8 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

  • Surface Aggregate Visible, from 02 to 03 o'clock, within 8 inches of joint: NO, Start - SEVERE AGG

    606.6 ft. - Surface Aggregate Visible, from 02 to 03 o'clock, within 8 inches of joint: NO, Start - SEVERE AGG

  • Surface Aggregate Visible, from 09 to 10 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    606.6 ft. - Surface Aggregate Visible, from 09 to 10 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    628.4 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    628.4 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES, Start - LONG REBAR

    633.2 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES, Start - LONG REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM

    640.1 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - CIRCUM

    646.1 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - CIRCUM

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - CIRCUM

    649.4 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - CIRCUM

Observations (42)

DistanceCodeObservation
640.1SRCCIRCUM
606.6SAVSEVERE AGG
649.4SRCCIRCUM
640.1SRVCIRCUM REBAR
628.4SRVCIRCUM REBAR
15.1SAPSEVERE AGG
380.3SSSPEELING CONCRETE
2SSSBLISTERING PEELING CONCRETE
452MWM
87.2MGOMAG COAT 40% START
606.6SAVSEVERE AGG
317.3MGOMAG COAT 40% FINISH
0MWM
628.4SAMSEVERE AGG
663.7AMH5:50AM
329.2SAVSEVERE AGG SPORATIC
29.2SAVSEVER AGG
15.1SAVSEVERE AGG
0AMH4:15AM
663.1SRVLONG REBAR
628.4SAV
2SAPSEVERE AGG
633.2SRVLONG REBAR
628.4SRVCIRCUM REBAR
29.2MGOUNUSAL RUST ON CONCRETE
628.4SSS
452SAPSEVERE AGG
663.1SRCCIRCUM REBAR
343.1SAPSEVERE AGG
329.2SSS
312SAVSEVERE AGG SPORATIC
29.2SSSBLISTERING PEELING CONCRETE
646.1SRCCIRCUM
0MWL
231.1SSSBLISTERING CONCRETE
556.8SSSBLISTERING CONCRETE
663.1SAMSEVERE AGG
359.2SAPSEVERE AGG
628.4SAV
343.1SAVSEVERE AGG
134.1SSSPEELING CONCRETE
628.4MWM

Properties (4)

custom_field_three
CORRODED REBAR CIRCUM
custom_field_two
2
customer
LACSD
datetime
2016-06-22T03:59:55-07:00