Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 22, 2016, 10:28 AM
  • A 0304_A 0303_6222016_041923.mp4

Date
06/22/2016
W/O
0574368
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00325
PipeID
P08214
Time
3:28 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
HO166
Sewer Name
A JOA-1A SAN JOSE CREEK WRP INTERCEPTOR
City
WHITTIER
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
15
Purpose
Capital Improvement Program Assesment
Project
20160621MDM_JOA_1A_SAN_JOSE_CREEK_WRP_INTERCEPTOR
Material
Reinforced Concrete Pipe
Shape
Circular
Height
63 in.
Upstream MH
A 0303
Downstream MH
A 0304
Dir. of Survey
Upstream
Length Surveyed
8 ft.
Total Length
8 ft.
Structural Index
3
Structural Quick
3221
Structural Rating
8
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
12
Pipe schematic from manhole A 0303 to A 0304
MH: A 0303MH: A 0304upstream0 ft. MSA - Survey Abandoned - UPLEG DOWNSTREAM SIPHON2 ft. SAV - Surface Aggregate Visible, from 01 to 02 o'clock, within 8 inches of joint: NO - 1 SEVERE AGG2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES - BLISTERING PEELING CONCRETE2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVER AGG6 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG8 ft. AMH - Upstream Manhole, Survey Begins - 3:50AM8 ft. MWM - Water Mark, 60 %of cross sectional area8 ft. MWL - Water Level, 50 %of cross sectional area

Observation photos (4)

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Aggregate Visible, from 01 to 02 o'clock, within 8 inches of joint: NO - 1 SEVERE AGG

    6 ft. - Surface Aggregate Visible, from 01 to 02 o'clock, within 8 inches of joint: NO - 1 SEVERE AGG

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES - BLISTERING PEELING CONCRETE

    6 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES - BLISTERING PEELING CONCRETE

  • Survey Abandoned - UPLEG DOWNSTREAM SIPHON

    8 ft. - Survey Abandoned - UPLEG DOWNSTREAM SIPHON

Observations (8)

DistanceCodeObservation
6SAV1 SEVERE AGG
8MSAUPLEG DOWNSTREAM SIPHON
6SSSBLISTERING PEELING CONCRETE
0AMH3:50AM
0MWM
2SAVSEVERE AGG
6SAVSEVER AGG
0MWL

Properties (5)

additional_info
UPLEG DOWNSTREAM SIPHON
custom_field_three
SEVERE AGG
custom_field_two
3
customer
LACSD
datetime
2016-06-22T03:28:39-07:00