- Date
- 06/18/2016
- W/O
- 0574862
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00325
- PipeID
- P08292
- Time
- 7:29 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- G6722
- Sewer Name
- A JOA-1A SAN JOSE CREEK WRP INTERCEPTOR
- City
- SAN GABRIEL
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 15
- Page No.
- 29
- Purpose
- Capital Improvement Program Assesment
- Project
- 20160618MDM_JOA_1A_SAN_JOSE_CREEK_WRP_INTERCEPTOR
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 24 in.
- Upstream MH
- A 0382
- Downstream MH
- A 0381
- Dir. of Survey
- Downstream
- Length Surveyed
- 3 ft.
- Total Length
- 3 ft.
- Structural Index
- 2
- Structural Quick
- 2100
- Structural Rating
- 2
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 2
Pipe schematic from manhole A 0382 to A 0381 Observation photos (3)

0 ft. - Water Mark, 20 %of cross sectional area

2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - SWOLLEN LAITANCE COAT

3 ft. - Survey Abandoned - DOWNLEG UPSTREAM SIPHON