Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 17, 2016, 03:27 PM
  • 05 1258_05 1257_6172016_083305.mp4

Date
06/17/2016
W/O
0574349
Weather
Dry
Operator/Surveyor
MIRANDA
Sewer ID
Z00518
PipeID
P06467
Time
8:27 AM
Certificate
U-1014-06022542
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7153
Sewer Name
05 SO HAWTHORNE-WARFIELD AV EXT TR, SECT 4
City
REDONDO BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
19
Purpose
Routine Assessment
Project
20160616AM_SO_HAWTHORNE_WARFIELD_AV_EXT_TR_SECT_4
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
05 1258
Downstream MH
05 1257
Dir. of Survey
Downstream
Length Surveyed
200.7 ft.
Total Length
200.7 ft.
Structural Index
3
Structural Quick
4336
Structural Rating
36
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
42
Pipe schematic from manhole 05 1258 to 05 1257
MH: 05 1258MH: 05 1257downstream0 ft. MWL - Water Level, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 8:29 AM0 ft. MWM - Water Mark, 50 %of cross sectional area12.3 ft. CM - Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES27.7 ft. CM - Crack Multiple, from 12 to 01 o'clock, within 8 inches of joint: YES38.8 ft. CM - Crack Multiple, from 10 to 01 o'clock, within 8 inches of joint: YES48.1 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES53.2 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES58.2 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES63.1 ft. CM - Crack Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES68.1 ft. FM - Fracture Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES78.3 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES88.2 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start128.4 ft. MGP - General Photograph - MULTIPLE CRACKS163.6 ft. FM - Fracture Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN198.9 ft. FM - Fracture Multiple, from 11 to 02 o'clock, within 8 inches of joint: YES200.7 ft. MGO - General Observation - SLIGHT GREASE THROUGHOUT THE REACH200.7 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish200.7 ft. MSA - Survey Abandoned - CANNOT TRACTOR PAST THE PROTRUDING BREAK-IN CONN.200.7 ft. TBI - Tap Break-In Intruding, at 10 o'clock, -, -, within 8 inches of joint: NO, 8", 2" - ACTIVE

Observation photos (7)

  • Fracture Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

    68.1 ft. - Fracture Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    88.2 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Photograph - MULTIPLE CRACKS

    128.4 ft. - General Photograph - MULTIPLE CRACKS

  • Fracture Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN

    163.6 ft. - Fracture Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN

  • Fracture Multiple, from 11 to 02 o'clock, within 8 inches of joint: YES

    198.9 ft. - Fracture Multiple, from 11 to 02 o'clock, within 8 inches of joint: YES

  • Survey Abandoned - CANNOT TRACTOR PAST THE PROTRUDING BREAK-IN CONN.

    200.7 ft. - Survey Abandoned - CANNOT TRACTOR PAST THE PROTRUDING BREAK-IN CONN.

  • Tap Break-In Intruding, at 10 o'clock, -, -, within 8 inches of joint: NO, 8", 2" - ACTIVE

    200.7 ft. - Tap Break-In Intruding, at 10 o'clock, -, -, within 8 inches of joint: NO, 8", 2" - ACTIVE

Observations (20)

DistanceCodeObservation
198.9FM
88.2CM
0MWL
63.1CM
53.2CL
200.7MGOSLIGHT GREASE THROUGHOUT THE REACH
68.1FM
27.7CM
200.7CM
78.3CM
0AMH8:29 AM
163.6FMPOSSIBLY BROKEN
128.4MGPMULTIPLE CRACKS
12.3CM
200.7MSACANNOT TRACTOR PAST THE PROTRUDING BREAK-IN CONN.
38.8CM
200.7TBIACTIVE
58.2CL
48.1CL
0MWM

Properties (4)

custom_field_three
BROKEN PIPE, PROTRUDING LOCAL LINE-2"
custom_field_two
1
customer
LACSD
datetime