Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 14, 2016, 06:54 AM
  • 29 0322_29 0321_6132016_035007.mp4

Date
06/13/2016
W/O
0568847
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z01024
PipeID
P24339
Time
11:54 PM
Certificate
U-1014-0602253
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0163
Sewer Name
29 PACIFIC COAST HIGHWAY TRUNK
City
LONG BEACH
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
03
Purpose
Routine Assessment
Project
20160614MDM_PACFIC_COAST_HIGHWAY_TRUNK
Material
NRCP
Shape
Circular
Height
8 in.
Upstream MH
29 0321
Downstream MH
29 0322
Dir. of Survey
Upstream
Length Surveyed
330.8 ft.
Total Length
330.8 ft.
Structural Index
3
Structural Quick
3A23
Structural Rating
36
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
36
Pipe schematic from manhole 29 0321 to 29 0322
MH: 29 0321MH: 29 0322upstream0 ft. AMH - Downstream Manhole, Survey Ends - 5:45AM0.5 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - MODERATE AGG0.5 ft. MGO - General Observation - CAMERA FLIPPED OVER 3 TIMES0.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG SPORATIC15.2 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - SLIGHT25.1 ft. SAP - Surface Aggregate Projecting, from 02 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC119.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open147.4 ft. FC - Fracture Circumferential, from 11 to 12 o'clock, within 8 inches of joint: YES - SLIGHT174.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC194.2 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - HAIRLINE196.8 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - HAIRLINE210.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open222.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SLIGHT250.5 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - SLIGHT251.2 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - HAIRLINE292.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN298.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG SPORATIC309.7 ft. FC - Fracture Circumferential, from 04 to 05 o'clock, within 8 inches of joint: YES - SLIGHT312.2 ft. MMC - Material Change, Concrete pipe (non-reinfored)315.9 ft. MMC - Material Change, Vitrified clay pipe320.6 ft. MGO - General Observation - 8" NRCP328.8 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active328.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - MODERATE AGG328.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC330.8 ft. AMH - Downstream Manhole, Survey Begins - 3:25AM330.8 ft. MWL - Water Level, 10 %of cross sectional area330.8 ft. MWM - Water Mark, 20 %of cross sectional area

Observation photos (8)

  • General Observation - Conn. @ Mh, 9 O' Clock. Active

    2 ft. - General Observation - Conn. @ Mh, 9 O' Clock. Active

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - MODERATE AGG

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - MODERATE AGG

  • General Observation - 8" NRCP

    10.2 ft. - General Observation - 8" NRCP

  • Material Change, Vitrified clay pipe

    14.9 ft. - Material Change, Vitrified clay pipe

  • Material Change, Concrete pipe (non-reinfored)

    18.6 ft. - Material Change, Concrete pipe (non-reinfored)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG SPORATIC

    32.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG SPORATIC

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

    156.2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

  • Surface Aggregate Projecting, from 02 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

    305.7 ft. - Surface Aggregate Projecting, from 02 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

Observations (28)

DistanceCodeObservation
330.3MGOConn. @ Mh, 9 O' Clock. Active
10.2MGO8" NRCP
2MGOConn. @ Mh, 9 O' Clock. Active
0AMH3:25AM
183.4FCSLIGHT
120.4TFOpen
134FLHAIRLINE
108.5FLSLIGHT
330.3SAPMODERATE AGG
2SAPMODERATE AGG
211TFOpen
2SAPSEVERE AGG SPORATIC
330.3MGOCAMERA FLIPPED OVER 3 TIMES
79.6FLHAIRLINE
330.8AMH5:45AM
305.7SAPSEVERE AGG SPORATIC
136.6FLHAIRLINE
156.2SAPSEVERE AGG SPORATIC
0MWL
32.1SAPSEVERE AGG SPORATIC
14.9MMC
330.3SAPSEVERE AGG SPORATIC
21.1FCSLIGHT
38.3TFOPEN
315.6FCSLIGHT
18.6MMC
0MWM
80.3FLSLIGHT

Properties (4)

custom_field_three
SEVERE AGG PROJECTING
custom_field_two
3
customer
LACSD
datetime
2016-06-13T23:54:48-07:00