Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 13, 2016, 10:14 AM
  • A 0385_A 0384_6132016_034321.mp4

Date
06/13/2016
W/O
0577469
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00325
PipeID
P08295
Time
3:14 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0159
Sewer Name
A JOA-1A SAN JOSE CREEK WRP INTERCEPTOR
City
SAN GABRIEL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
01
Purpose
Capital Improvement Program Assesment
Project
20160611MDM_JOA_1A_SAN_JOSE_CREEK_WRP_INTERCEPTOR
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Upstream MH
A 0385
Downstream MH
A 0384
Dir. of Survey
Downstream
Length Surveyed
431.7 ft.
Total Length
431.7 ft.
Structural Index
4
Structural Quick
5232
Structural Rating
18
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
18
Pipe schematic from manhole A 0385 to A 0384
MH: A 0385MH: A 0384downstream0 ft. AMH - Upstream Manhole, Survey Begins - 3:40AM0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SWOLLEN BLISTERING PEELING CONCRETE8 ft. MGO - General Observation - MAG COAT 60% START 8:00 TO 4:008 ft. SAV - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC9 ft. SRV - Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR POSSIBLE12.1 ft. MGO - General Observation - MAG COAT 70% START254.3 ft. MGO - General Observation - MAG COAT 40% START271.7 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO, Start - CIRCUM REBAR279.7 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO, Finish348.3 ft. MGO - General Observation - MAG COAT 70% START391.4 ft. SAV - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG431.1 ft. MGO - General Observation - 70% MAG COAT FINISH431.1 ft. SAV - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG SPORATIC431.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SWOLLEN BLISTERING PEELING CONCRETE431.7 ft. AMH - Downstream Manhole, Survey Ends - 4:15AM

Observation photos (9)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SWOLLEN BLISTERING  PEELING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SWOLLEN BLISTERING PEELING CONCRETE

  • General Observation - MAG COAT 60% START  8:00 TO 4:00

    8 ft. - General Observation - MAG COAT 60% START 8:00 TO 4:00

  • Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

    8 ft. - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

  • Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR POSSIBLE

    9 ft. - Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR POSSIBLE

  • General Observation - MAG COAT 70% START

    12.1 ft. - General Observation - MAG COAT 70% START

  • General Observation - MAG COAT 40% START

    254.3 ft. - General Observation - MAG COAT 40% START

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO, Start - CIRCUM REBAR

    271.7 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO, Start - CIRCUM REBAR

  • General Observation - MAG COAT 70% START

    348.3 ft. - General Observation - MAG COAT 70% START

  • Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

    391.4 ft. - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

Observations (17)

DistanceCodeObservation
2SSSSWOLLEN BLISTERING PEELING CONCRETE
391.4SAVSEVERE AGG
271.7SRVCIRCUM REBAR
0AMH3:40AM
0MWL
431.7AMH4:15AM
8MGOMAG COAT 60% START 8:00 TO 4:00
431.1MGO70% MAG COAT FINISH
254.3MGOMAG COAT 40% START
8SAVSEVERE AGG SPORATIC
0MWM
12.1MGOMAG COAT 70% START
348.3MGOMAG COAT 70% START
279.7SRV
431.1SAVSEVERE AGG SPORATIC
431.1SSSSWOLLEN BLISTERING PEELING CONCRETE
9SRVCIRCUM REBAR POSSIBLE

Properties (4)

custom_field_three
CIRCUM REBAR-SEVERE AGG SPOATIC-70% MAG COAT
custom_field_two
2
customer
LACSD
datetime
2016-06-13T03:14:43-07:00