05 2216_05 1263_6152016_110425.mp4
3 ft. - Crack Spiral, from 01 to 04 o'clock, within 8 inches of joint: YES, Start
7.1 ft. - Crack Spiral, from 01 to 04 o'clock, within 8 inches of joint: YES, Finish - ENDS AS A FRACTURE
22.6 ft. - Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start
73.8 ft. - Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: YES, 6" - CAPPED, BROKEN
174.4 ft. - Deposits Attached Other, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES - DEBRIS
187.5 ft. - Deposits Attached Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES
269.3 ft. - Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish
270.8 ft. - Roots Medium Lateral, from 07 to 11 o'clock, 45 %, within 8 inches of joint: NO - TAP ROOTS COMING OUT OF THE CONN.
271.1 ft. - Survey Abandoned - INSPECTION COMPLETED ON A REVERSE PULL
| Distance | Code | Observation |
|---|---|---|
| 0 | MWL | STAGNANT WATER |
| 269.3 | MGO | SLIGHT GREASE/DEBRIS THROUGHOUT THE REACH |
| 0 | AMH | 11:01 AM |
| 22.6 | CM | — |
| 123 | TBA | — |
| 269.3 | CM | — |
| 0 | MGO | ACTIVE CONN. INSIDE THE MH. @ 09 O'CLOCK |
| 174.4 | DAZ | DEBRIS |
| 10.5 | CM | — |
| 187.5 | DAZ | — |
| 0 | MWM | — |
| 14.6 | CM | — |
| 271.1 | MSA | INSPECTION COMPLETED ON A REVERSE PULL |
| 7.1 | CS | ENDS AS A FRACTURE |
| 18.3 | CM | — |
| 270.8 | RML | TAP ROOTS COMING OUT OF THE CONN. |
| 73.8 | TFD | CAPPED, BROKEN |
| 185.3 | TBA | — |
| 69.9 | TFA | — |
| 3 | CS | — |