Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 9, 2016, 07:31 AM
  • 05 2275_05 0756_592016_011306.mp4

Date
05/09/2016
W/O
0563852
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00484
PipeID
P05983
Time
12:31 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0123
Sewer Name
05 MANCHESTER-VERMONT RELIEF TRUNK
City
LYNWOOD
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Capital Improvement Program Assesment
Project
20160509MDM_MANCHESTER_VERMONT_RELIEF_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
05 2275
Downstream MH
05 0756
Dir. of Survey
Downstream
Length Surveyed
235.9 ft.
Total Length
235.9 ft.
Structural Index
2
Structural Quick
342C
Structural Rating
50
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
50
Pipe schematic from manhole 05 2275 to 05 0756
MH: 05 2275MH: 05 0756downstream0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active OUGOING0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active INCOMING0 ft. MGO - General Observation - MH CONN 10;:00 OPEN0 ft. AMH - Upstream Manhole, Survey Begins - 12:35AM6 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SLIGHT6 ft. FC - Fracture Circumferential, from 11 to 12 o'clock, within 8 inches of joint: YES - SLIGHT8.9 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - H8.9 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - HAIRLINE8.9 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - MODERATE9.9 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, - H9.9 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, - H12.7 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - SLIGHT12.7 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - SLIGHT16.6 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - H16.6 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SLIGHT20.9 ft. FC - Fracture Circumferential, from 01 to 02 o'clock, within 8 inches of joint: YES - MODERATE20.9 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - SLIGHT24.7 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SLIGHT28.9 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - SLIGHT32.9 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - SLIGHT32.9 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - SLIGHT36.8 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - SLIGHT40.8 ft. FL - Fracture Longitudinal, at 08 TO 4 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS40.8 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - SLIGHT40.8 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS40.8 ft. FL - Fracture Longitudinal, at 08 TO 4 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS40.8 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS150.1 ft. MGO - General Observation - 15" VCP235.6 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Finish - 30% HAIRLINE235.6 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Finish - 50% HAIRLINE235.6 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 80% SLIGHT235.6 ft. FL - Fracture Longitudinal, at 08 TO 4 o'clock, within 8 inches of joint: YES, Finish - 30% SLIGHT235.9 ft. AMH - Downstream Manhole, Survey Ends - 1:05AM

Observation photos (3)

  • Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - MODERATE

    8.9 ft. - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - MODERATE

  • Fracture Circumferential, from 01 to 02 o'clock, within 8 inches of joint: YES - MODERATE

    20.9 ft. - Fracture Circumferential, from 01 to 02 o'clock, within 8 inches of joint: YES - MODERATE

  • General Observation - 15" VCP

    150.1 ft. - General Observation - 15" VCP

Observations (35)

DistanceCodeObservation
0MGOConn. @ Mh, 3 O' Clock. Active OUGOING
8.9FCH
40.8FLSLIGHT AT JOINTS
235.6FL30% HAIRLINE
40.8FCSLIGHT
235.6FL50% HAIRLINE
6FCSLIGHT
0MWL
12.7FCSLIGHT
20.9FCMODERATE
0MWM
28.9FCSLIGHT
9.9FLH
36.8FCSLIGHT
40.8FCSLIGHT AT JOINTS
16.6FCH
0MGOConn. @ Mh, 9 O' Clock. Active INCOMING
150.1MGO15" VCP
9.9FLH
8.9FCHAIRLINE
6FCSLIGHT
235.9AMH1:05AM
40.8FLHAIRLINE AT JOINTS
32.9FCSLIGHT
12.7FCSLIGHT
32.9FCSLIGHT
8.9FCMODERATE
235.6FC80% SLIGHT
0MGOMH CONN 10;:00 OPEN
40.8FCHAIRLINE AT JOINTS
235.6FL30% SLIGHT
0AMH12:35AM
16.6FCSLIGHT
24.7FCSLIGHT
20.9FCSLIGHT

Properties (4)

custom_field_three
MODERATE FRACTURES - MULTIPLE SLIGHT
custom_field_two
2
customer
LACSD
datetime
2016-05-09T00:31:34-07:00