Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 9, 2016, 04:25 PM
  • C 0315_C 0314_592016_092914.mp4

Date
05/09/2016
W/O
0563383
Weather
Light Rain
Operator/Surveyor
MIRANDA
Sewer ID
Z00135
PipeID
P09778
Time
9:25 AM
Certificate
U-1014-06022542
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7112
Sewer Name
C JOINT OUTFALL C - UNIT 6F
City
CERRITOS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
04
Purpose
Routine Assessment
Project
20160506AM_JOINT_OUTFALL_C_UNIT_6F
Material
Reinforced Concrete Pipe
Shape
Circular
Height
15 in.
Upstream MH
C 0315
Downstream MH
C 0314
Dir. of Survey
Downstream
Length Surveyed
314.6 ft.
Total Length
314.6 ft.
Structural Index
5
Structural Quick
5B33
Structural Rating
91
O&M Index
3
O&M Quick
3200
O&M Rating
6
Overall Index
4
Overall Quick
Overall Rating
97
Pipe schematic from manhole C 0315 to C 0314
MH: C 0315MH: C 0314downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - ROACHES INSIDE THE MH.0 ft. AMH - Upstream Manhole, Survey Begins - 9:28 AM0 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO, Start2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start35.3 ft. SRV - Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: YES36.7 ft. SRV - Surface Reinforcement Visible, from 11 to 02 o'clock, within 8 inches of joint: YES, Start38.9 ft. MGP - General Photograph - REBAR43.8 ft. SRV - Surface Reinforcement Visible, from 11 to 02 o'clock, within 8 inches of joint: YES, Finish46.8 ft. SRV - Surface Reinforcement Visible, from 09 to 11 o'clock, within 8 inches of joint: YES, Start49.4 ft. MGO - General Observation - REBAR51.7 ft. TBD - Tap Break-In Defective, at 03 o'clock, -, , within 8 inches of joint: YES, 6" - ACTIVE, CRACKED52.8 ft. SRV - Surface Reinforcement Visible, from 09 to 11 o'clock, within 8 inches of joint: YES, Finish62.5 ft. SRV - Surface Reinforcement Visible, from 09 to 11 o'clock, within 8 inches of joint: YES, Start63.9 ft. MGP - General Photograph - REBAR/CORROSION69.2 ft. SRV - Surface Reinforcement Visible, from 09 to 12 o'clock, within 8 inches of joint: YES, Finish107 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN109.2 ft. SRV - Surface Reinforcement Visible, at 11 o'clock, within 8 inches of joint: NO157 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"173.8 ft. SRV - Surface Reinforcement Visible, at 01 o'clock, within 8 inches of joint: NO179.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES181.4 ft. SRV - Surface Reinforcement Visible, from 12 to 04 o'clock, within 8 inches of joint: YES190.3 ft. SRV - Surface Reinforcement Visible, at 10 o'clock, within 8 inches of joint: NO194.4 ft. SRV - Surface Reinforcement Visible, from 01 to 04 o'clock, within 8 inches of joint: YES195.7 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start202.3 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish209.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES209.5 ft. SRV - Surface Reinforcement Visible, at 09 o'clock, within 8 inches of joint: YES, Start212.5 ft. SRV - Surface Reinforcement Visible, at 09 o'clock, within 8 inches of joint: YES, Finish248.8 ft. SRV - Surface Reinforcement Visible, at 10 o'clock, within 8 inches of joint: NO, Start252.6 ft. SRV - Surface Reinforcement Visible, at 11 o'clock, within 8 inches of joint: YES262.8 ft. SRV - Surface Reinforcement Visible, at 10 o'clock, within 8 inches of joint: NO, Finish285.9 ft. SRV - Surface Reinforcement Visible, from 12 to 02 o'clock, within 8 inches of joint: YES297.9 ft. SRV - Surface Reinforcement Visible, at 11 o'clock, within 8 inches of joint: NO, Start302.2 ft. SRV - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: NO302.2 ft. SRV - Surface Reinforcement Visible, at 11 o'clock, within 8 inches of joint: NO, Finish314.1 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - OPEN314.1 ft. MGO - General Observation - CORRODED PIPE THROUGHOUT THE REACH314.1 ft. DAE - Deposits Attached Encrustation, 15 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES314.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish314.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish314.6 ft. MSA - Survey Abandoned - CALCIUM DEPOSITS

Observation photos (34)

  • Water Level, 20 %of cross sectional area

    0 ft. - Water Level, 20 %of cross sectional area

  • General Observation - ROACHES INSIDE THE MH.

    0 ft. - General Observation - ROACHES INSIDE THE MH.

  • Upstream Manhole, Survey Begins - 9:28 AM

    0 ft. - Upstream Manhole, Survey Begins - 9:28 AM

  • Water Mark, 30 %of cross sectional area

    0 ft. - Water Mark, 30 %of cross sectional area

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

  • Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: YES

    35.3 ft. - Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Visible, from 11 to 02 o'clock, within 8 inches of joint: YES, Start

    36.7 ft. - Surface Reinforcement Visible, from 11 to 02 o'clock, within 8 inches of joint: YES, Start

  • General Photograph - REBAR

    38.9 ft. - General Photograph - REBAR

  • Surface Reinforcement Visible, from 11 to 02 o'clock, within 8 inches of joint: YES, Finish

    43.8 ft. - Surface Reinforcement Visible, from 11 to 02 o'clock, within 8 inches of joint: YES, Finish

  • Surface Reinforcement Visible, from 09 to 11 o'clock, within 8 inches of joint: YES, Start

    46.8 ft. - Surface Reinforcement Visible, from 09 to 11 o'clock, within 8 inches of joint: YES, Start

  • General Observation - REBAR

    49.4 ft. - General Observation - REBAR

  • Tap Break-In Defective, at 03 o'clock, -,  , within 8 inches of joint: YES, 6" - ACTIVE, CRACKED

    51.7 ft. - Tap Break-In Defective, at 03 o'clock, -, , within 8 inches of joint: YES, 6" - ACTIVE, CRACKED

  • Surface Reinforcement Visible, from 09 to 11 o'clock, within 8 inches of joint: YES, Finish

    52.8 ft. - Surface Reinforcement Visible, from 09 to 11 o'clock, within 8 inches of joint: YES, Finish

  • Surface Reinforcement Visible, from 09 to 11 o'clock, within 8 inches of joint: YES, Start

    62.5 ft. - Surface Reinforcement Visible, from 09 to 11 o'clock, within 8 inches of joint: YES, Start

  • General Photograph - REBAR/CORROSION

    63.9 ft. - General Photograph - REBAR/CORROSION

  • Surface Reinforcement Visible, from 09 to 12 o'clock, within 8 inches of joint: YES, Finish

    69.2 ft. - Surface Reinforcement Visible, from 09 to 12 o'clock, within 8 inches of joint: YES, Finish

  • Surface Reinforcement Visible, at 11 o'clock, within 8 inches of joint: NO

    109.2 ft. - Surface Reinforcement Visible, at 11 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, at 01 o'clock, within 8 inches of joint: NO

    173.8 ft. - Surface Reinforcement Visible, at 01 o'clock, within 8 inches of joint: NO

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

    179.4 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Visible, from 12 to 04 o'clock, within 8 inches of joint: YES

    181.4 ft. - Surface Reinforcement Visible, from 12 to 04 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Visible, at 10 o'clock, within 8 inches of joint: NO

    190.3 ft. - Surface Reinforcement Visible, at 10 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, from 01 to 04 o'clock, within 8 inches of joint: YES

    194.4 ft. - Surface Reinforcement Visible, from 01 to 04 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

    195.7 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

    209.3 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Visible, at 09 o'clock, within 8 inches of joint: YES, Start

    209.5 ft. - Surface Reinforcement Visible, at 09 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, at 10 o'clock, within 8 inches of joint: NO, Start

    248.8 ft. - Surface Reinforcement Visible, at 10 o'clock, within 8 inches of joint: NO, Start

  • Surface Reinforcement Visible, at 11 o'clock, within 8 inches of joint: YES

    252.6 ft. - Surface Reinforcement Visible, at 11 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Visible, at 10 o'clock, within 8 inches of joint: NO, Finish

    262.8 ft. - Surface Reinforcement Visible, at 10 o'clock, within 8 inches of joint: NO, Finish

  • Surface Reinforcement Visible, from 12 to 02 o'clock, within 8 inches of joint: YES

    285.9 ft. - Surface Reinforcement Visible, from 12 to 02 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Visible, at 11 o'clock, within 8 inches of joint: NO, Start

    297.9 ft. - Surface Reinforcement Visible, at 11 o'clock, within 8 inches of joint: NO, Start

  • Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: NO

    302.2 ft. - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: NO

  • Deposits Attached Encrustation, 15 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES

    314.1 ft. - Deposits Attached Encrustation, 15 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES

  • Survey Abandoned - CALCIUM DEPOSITS

    314.6 ft. - Survey Abandoned - CALCIUM DEPOSITS

Observations (43)

DistanceCodeObservation
173.8SRV
285.9SRV
297.9SRV
157TFA
2SSS
46.8SRV
181.4SRV
248.8SRV
109.2SRV
52.8SRV
202.3SRV
49.4MGOREBAR
194.4SRV
2SAV
107TBOPEN
314.1TFOPEN
62.5SRV
35.3SRV
0MWL
0MGOROACHES INSIDE THE MH.
179.4SAV
314.1MGOCORRODED PIPE THROUGHOUT THE REACH
0AMH9:28 AM
212.5SRV
69.2SRV
195.7SRV
209.3SAV
314.1DAE
302.2SRV
36.7SRV
209.5SRV
38.9MGPREBAR
302.2SRV
314.1SAV
252.6SRV
63.9MGPREBAR/CORROSION
43.8SRV
262.8SRV
51.7TBDACTIVE, CRACKED
314.6MSACALCIUM DEPOSITS
190.3SRV
0MWM
314.1SSS

Properties (4)

custom_field_three
REBAR/CORRODED PIPE
custom_field_two
1
customer
LACSD
datetime
2016-05-09T09:25:00-07:00