Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 4, 2016, 07:29 AM
  • 05 0761_05 0760_542016_004613.mp4

Date
05/04/2016
W/O
0563852
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00484
PipeID
P05988
Time
12:29 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0120
Sewer Name
05 MANCHESTER-VERMONT RELIEF TRUNK
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Capital Improvement Program Assesment
Project
20160503MDM_MANCHESTER_VERMONT_RELIEF_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
05 0761
Downstream MH
05 0760
Dir. of Survey
Downstream
Length Surveyed
402.9 ft.
Total Length
402.9 ft.
Structural Index
2
Structural Quick
322B
Structural Rating
38
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
38
Pipe schematic from manhole 05 0761 to 05 0760
MH: 05 0761MH: 05 0760downstream0 ft. AMH - Upstream Manhole, Survey Begins - 12:30AM0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area6.5 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SLIGHT11.1 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - HAIRLINE11.1 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES14.6 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - SLIGHT14.6 ft. FC - Fracture Circumferential, from 11 to 12 o'clock, within 8 inches of joint: YES - H22.6 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - HAIRLINE22.6 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - SLIGHT26.7 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - SLIGHT30.7 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - H30.7 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SLIGHT38.7 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SLIGHT42.7 ft. FL - Fracture Longitudinal, at 08 TO 4 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS42.7 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS42.7 ft. FL - Fracture Longitudinal, at 08 TO 4 o'clock, within 8 inches of joint: YES, Start - SLIGHT AT JOINTS42.7 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - H42.7 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - SLIGHT42.7 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS200.2 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - MODERATE389.3 ft. MGO - General Observation - 15" VCP402.6 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 70% HAIRLINE AT JOINTS402.6 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Finish - 20% HAIRLINE AT JOINTS402.6 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Finish - 30% SLIGHT AT JOINTS402.6 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 90% SLIGHT AT JOINTS402.9 ft. AMH - Downstream Manhole, Survey Ends - 1:35AM

Observation photos (2)

  • Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - MODERATE

    200.2 ft. - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - MODERATE

  • General Observation - 15" VCP

    389.3 ft. - General Observation - 15" VCP

Observations (27)

DistanceCodeObservation
22.6FCHAIRLINE
402.6FC70% HAIRLINE AT JOINTS
30.7FCH
402.6FL20% HAIRLINE AT JOINTS
402.9AMH1:35AM
0AMH12:30AM
26.7FCSLIGHT
42.7FLHAIRLINE AT JOINTS
11.1FCHAIRLINE
42.7FCSLIGHT AT JOINTS
389.3MGO15" VCP
200.2FCMODERATE
42.7FLSLIGHT AT JOINTS
30.7FCSLIGHT
0MWL
38.7FCSLIGHT
42.7FCH
14.6FCSLIGHT
42.7FCSLIGHT
402.6FL30% SLIGHT AT JOINTS
22.6FCSLIGHT
402.6FC90% SLIGHT AT JOINTS
14.6FCH
0MWM
42.7FCHAIRLINE AT JOINTS
11.1FC
6.5FCSLIGHT

Properties (4)

custom_field_three
SLIGHT FRACTURES 1 MODERATE
custom_field_two
2
customer
LACSD
datetime