Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 11, 2016, 09:12 AM
Date
04/11/2016
W/O
0557603
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00488
PipeID
P06301
Time
2:12 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6684
Sewer Name
05 MONETA EXTENSION TRUNK, SECTION 1
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
21
Purpose
Routine Assessment
Project
20160408MDM_MONETA_EXTENSION_TRUNK_SECTION_1
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Upstream MH
05 1067
Downstream MH
05 1066
Dir. of Survey
Downstream
Length Surveyed
435.8 ft.
Total Length
435.8 ft.
Structural Index
2
Structural Quick
2812
Structural Rating
18
O&M Index
2
O&M Quick
412Q
O&M Rating
180
Overall Index
2
Overall Quick
Overall Rating
198
Pipe schematic from manhole 05 1067 to 05 1066
MH: 05 1067MH: 05 1066downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - MH CONN ACTIVE 3:000 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 2:55AM2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES8 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES76 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 6", 6" - ACTIVE103.4 ft. MGO - General Observation - 24" VCP103.4 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES143.7 ft. DSGV - Deposits Settled Gravel, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES163.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE207.5 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - SLIGHT210.8 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - HAIRLINE212.2 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - HAIRLINE212.2 ft. CC - Crack Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES238.6 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE293.1 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES293.5 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES294.5 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE330.1 ft. CC - Crack Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES349.1 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 6" - OPEN405.7 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 6" - OPEN435.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish435.8 ft. AMH - Downstream Manhole, Survey Ends - 3:30AM

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - 24" VCP

    103.4 ft. - General Observation - 24" VCP

Observations (25)

DistanceCodeObservation
0MWL
294.5TBACTIVE
293.5CL
330.1CC
210.8FCHAIRLINE
349.1TBOPEN
2DAGS
163.9TFACTIVE
143.7DSGV
435.1DAGS
8CL
0MGOMH CONN ACTIVE 3:00
103.4MGO24" VCP
103.4CL
0MWM
212.2FCHAIRLINE
76TBACTIVE
405.7TBOPEN
207.5FCSLIGHT
293.1CL
0AMH2:55AM
435.8AMH3:30AM
238.6TBACTIVE
212.2CC
8CL

Properties (3)

custom_field_two
4
customer
LACSD
datetime
2016-04-11T02:12:59-07:00