Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 8, 2016, 08:35 AM
Date
04/08/2016
W/O
0557603
Weather
Light Rain
Operator/Surveyor
MARTIN
Sewer ID
Z00488
PipeID
P06305
Time
1:35 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6681
Sewer Name
05 MONETA EXTENSION TRUNK, SECTION 1
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
21
Purpose
Routine Assessment
Project
20160408MDM_MONETA_EXTENSION_TRUNK_SECTION_1
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Upstream MH
05 1071
Downstream MH
05 1070
Dir. of Survey
Downstream
Length Surveyed
453.6 ft.
Total Length
453.6 ft.
Structural Index
2
Structural Quick
342A
Structural Rating
37
O&M Index
2
O&M Quick
412Q
O&M Rating
184
Overall Index
2
Overall Quick
Overall Rating
221
Pipe schematic from manhole 05 1071 to 05 1070
MH: 05 1071MH: 05 1070downstream0 ft. AMH - Upstream Manhole, Survey Begins - 1:45AM0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - MH CONN ACTIVE 9:000 ft. MWM - Water Mark, 60 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start19.3 ft. CC - Crack Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES19.3 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - HAIRLINE28.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - STUB35.2 ft. MGO - General Observation - WHITE BULDUP GROWING ON PIPE38.6 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - HAIRLINE42.5 ft. CC - Crack Circumferential, from 12 to 01 o'clock, within 8 inches of joint: YES50.4 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES57.9 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES120.7 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES120.7 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES124.9 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - HAIRLINE124.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - STUB140.1 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - HAIRLINE143.6 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES155.9 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES219.9 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - HAIRLINE225.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - STUB278.1 ft. MGO - General Observation - 24" VCP326.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - STUB369.3 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - HAIRLINE408.6 ft. CC - Crack Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES416.2 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES432 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES444 ft. CC - Crack Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES447.5 ft. CC - Crack Circumferential, from 11 to 12 o'clock, within 8 inches of joint: YES453.2 ft. MGO - General Observation - MH CONN ACTIVE OUTGOING LINE 9:00453.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish453.2 ft. MGO - General Observation - MH CONN ACTIVE 3:00453.6 ft. AMH - Downstream Manhole, Survey Ends - 2:30AM

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - WHITE BULDUP GROWING ON PIPE

    35.2 ft. - General Observation - WHITE BULDUP GROWING ON PIPE

  • General Observation - 24" VCP

    278.1 ft. - General Observation - 24" VCP

Observations (34)

DistanceCodeObservation
120.7CL
278.1MGO24" VCP
369.3FLHAIRLINE
28.3TFCSTUB
0AMH1:45AM
143.6CL
155.9CL
0MWL
447.5CC
225.1TFCSTUB
432CL
0MGOMH CONN ACTIVE 9:00
219.9FCHAIRLINE
120.7CL
453.2MGOMH CONN ACTIVE OUTGOING LINE 9:00
19.3CC
42.5CC
124.9FCHAIRLINE
453.2DAGS
408.6CC
38.6FLHAIRLINE
416.2CL
444CC
326.2TFCSTUB
0MWM
35.2MGOWHITE BULDUP GROWING ON PIPE
453.6AMH2:30AM
140.1FLHAIRLINE
19.3FLHAIRLINE
2DAGS
124.9TFCSTUB
453.2MGOMH CONN ACTIVE 3:00
57.9CL
50.4CL

Properties (3)

custom_field_two
4
customer
LACSD
datetime
2016-04-08T01:35:00-07:00