Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 5, 2016, 09:15 AM
Date
04/05/2016
W/O
0557603
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00488
PipeID
P06307
Time
2:15 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6677
Sewer Name
05 MONETA EXTENSION TRUNK, SECTION 1
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
21
Purpose
Routine Assessment
Project
20160405MDM_MONETA_EXTENSION_TRUNK_SECTION_1
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Upstream MH
05 1073
Downstream MH
05 1072
Dir. of Survey
Downstream
Length Surveyed
260.7 ft.
Total Length
260.7 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
2
O&M Quick
412I
O&M Rating
108
Overall Index
2
Overall Quick
Overall Rating
110
Pipe schematic from manhole 05 1073 to 05 1072
MH: 05 1073MH: 05 1072downstream0 ft. AMH - Upstream Manhole, Survey Begins - 4:45AM0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start87.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - STUB87.7 ft. MGO - General Observation - 24" VCP188.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - STUB191.2 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - HAIRLINE260.2 ft. MGO - General Observation - MH CONN 9:00 STUB260.2 ft. MGO - General Observation - MH CONN ACTIVE 8:00260.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish260.7 ft. AMH - Downstream Manhole, Survey Ends - 5:05AM

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - 24" VCP

    87.7 ft. - General Observation - 24" VCP

Observations (12)

DistanceCodeObservation
2DAGS
260.2MGOMH CONN 9:00 STUB
87.7TFCSTUB
0AMH4:45AM
0MWM
0MWL
87.7MGO24" VCP
188.9TFCSTUB
260.2MGOMH CONN ACTIVE 8:00
260.7AMH5:05AM
191.2FCHAIRLINE
260.2DAGS

Properties (3)

custom_field_two
4
customer
LACSD
datetime
2016-04-05T02:15:46-07:00