Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 5, 2016, 09:14 AM
Date
04/05/2016
W/O
0557603
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00488
PipeID
P06308
Time
2:14 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6677
Sewer Name
05 MONETA EXTENSION TRUNK, SECTION 1
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
21
Purpose
Routine Assessment
Project
20160405MDM_MONETA_EXTENSION_TRUNK_SECTION_1
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Upstream MH
05 1074
Downstream MH
05 1073
Dir. of Survey
Downstream
Length Surveyed
232.5 ft.
Total Length
232.5 ft.
Structural Index
2
Structural Quick
2713
Structural Rating
17
O&M Index
2
O&M Quick
412H
O&M Rating
98
Overall Index
2
Overall Quick
Overall Rating
115
Pipe schematic from manhole 05 1074 to 05 1073
MH: 05 1074MH: 05 1073downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 3:50AM0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - MH CONN ACTIVE 3:002 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start15 ft. DSGV - Deposits Settled Gravel, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES21.6 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - STUB23.5 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - SLIGHT59.1 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES59.1 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES59.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES75.5 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES99 ft. CC - Crack Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES99 ft. CC - Crack Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES108.6 ft. MGO - General Observation - 24" VCP114.7 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES119 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - STUB125.8 ft. CC - Crack Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES169.5 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - SLIGHT220 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - STUB232 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish232.5 ft. AMH - Downstream Manhole, Survey Ends - 4:10AM

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - 24" VCP

    108.6 ft. - General Observation - 24" VCP

Observations (22)

DistanceCodeObservation
119TFCSTUB
21.6TFCSTUB
220TFCSTUB
232.5AMH4:10AM
99CC
108.6MGO24" VCP
0MWM
169.5FCSLIGHT
232DAGS
59.1CL
114.7CL
59.1CL
99CC
23.5FCSLIGHT
75.5CL
59.1CL
125.8CC
0AMH3:50AM
2DAGS
0MWL
15DSGV
0MGOMH CONN ACTIVE 3:00

Properties (3)

custom_field_two
4
customer
LACSD
datetime
2016-04-05T02:14:43-07:00