Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 19, 2016, 06:00 AM
  • J 0396_J 0395_3182016_001921.mp4

Date
03/18/2016
W/O
0557681
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00057
PipeID
P21088
Time
11:00 PM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0094
Sewer Name
J JOINT OUTFALL J - UNIT 1E
City
PALOS VERDES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
46
Purpose
Capital Improvement Program Assesment
Project
201603MDM_JOINT_OUTFALL_J_UNIT_1E
Material
Vitrified Clay Pipe
Shape
Circular
Height
27 in.
Upstream MH
J 0396
Downstream MH
J 0395
Dir. of Survey
Downstream
Length Surveyed
357.4 ft.
Total Length
357.4 ft.
Structural Index
3
Structural Quick
3A24
Structural Rating
41
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
41
Pipe schematic from manhole J 0396 to J 0395
MH: J 0396MH: J 0395downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 11:40PM54.7 ft. MGO - General Observation - 27" VCP75.8 ft. MGO - General Observation - THIN WHITE COATING OR BUILDUP ON PIPE START75.8 ft. MGP - General Photograph137.7 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start - HAIRLINE143.4 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Finish - HAIRLINE145.6 ft. FS - Fracture Spiral, from 12 to 05 o'clock, within 8 inches of joint: YES, Start - HAIRLINE155.2 ft. FS - Fracture Spiral, from 12 to 05 o'clock, within 8 inches of joint: YES, Finish - HAIRLINE159.2 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - SLIGHT159.2 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - HAIRLINE159.2 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - HAIRLINE164.4 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start - HAIRLINE179.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - HAIRLINE191.9 ft. FS - Fracture Spiral, from 12 to 02 o'clock, within 8 inches of joint: YES, Start - HAIRLINE191.9 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Finish - HAIRLINE227.1 ft. FS - Fracture Spiral, from 12 to 02 o'clock, within 8 inches of joint: YES, Finish - HAIRLINE234.7 ft. MGO - General Observation - WHITE COATING FINISH234.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - HAIRLINE241.6 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES, Start - HAIRLINE241.6 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - HAIRLINE250.4 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES, Finish - HAIRLINE255.3 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start - HAIRLINE266.8 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Finish269.7 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Start - HAIRLINE284.4 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Finish295.9 ft. FS - Fracture Spiral, from 10 to 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE295.9 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - HAIRLINE317.9 ft. FS - Fracture Spiral, from 10 to 12 o'clock, within 8 inches of joint: YES, Finish357.4 ft. AMH - Downstream Manhole, Survey Ends - 12:25AM

Observation photos (8)

  • General Observation - 27" VCP

    54.7 ft. - General Observation - 27" VCP

  • General Observation - THIN WHITE COATING OR BUILDUP ON PIPE START

    75.8 ft. - General Observation - THIN WHITE COATING OR BUILDUP ON PIPE START

  • General Photograph

    75.8 ft. - General Photograph

  • Fracture Spiral, from 12 to 05 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

    145.6 ft. - Fracture Spiral, from 12 to 05 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

  • Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

    164.4 ft. - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

  • Fracture Spiral, from 12 to 02 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

    191.9 ft. - Fracture Spiral, from 12 to 02 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

  • Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

    269.7 ft. - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

  • Fracture Spiral, from 10 to 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

    295.9 ft. - Fracture Spiral, from 10 to 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

Observations (31)

DistanceCodeObservation
295.9FSHAIRLINE
234.7MGOWHITE COATING FINISH
0MWM
75.8MGOTHIN WHITE COATING OR BUILDUP ON PIPE START
241.6FLHAIRLINE
137.7FLHAIRLINE
241.6FCHAIRLINE
269.7FLHAIRLINE
295.9FCHAIRLINE
357.4AMH12:25AM
284.4FL
191.9FSHAIRLINE
227.1FSHAIRLINE
155.2FSHAIRLINE
143.4FLHAIRLINE
266.8FL
255.3FLHAIRLINE
179.7FLHAIRLINE
317.9FS
0MWL
159.2FCSLIGHT
191.9FLHAIRLINE
145.6FSHAIRLINE
234.7FLHAIRLINE
75.8MGP
159.2FLHAIRLINE
54.7MGO27" VCP
250.4FLHAIRLINE
164.4FLHAIRLINE
0AMH11:40PM
159.2FCHAIRLINE

Properties (5)

custom_field_three
HAIRLINE SPRIAL JOINT TO JOINT LONGER
custom_field_two
2
customer
LACSD
datetime
2016-03-18T23:00:10-07:00
year_laid
19950221