- Date
- 03/22/2016
- W/O
- 0557605
- Weather
- Dry
- Operator/Surveyor
- MIRANDA
- Sewer ID
- Z00016
- PipeID
- P00056
- Time
- 10:10 AM
- Certificate
- U-1014-06022542
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- G7081
- Sewer Name
- 08 MAIN STREET TRUNK
- City
- CARSON
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 08
- Page No.
- 04
- Purpose
- Routine Assessment
- Project
- 20160322AM_MAIN_STREET_TRUNK
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 18 in.
- Upstream MH
- 08 0054
- Downstream MH
- 08 0053
- Dir. of Survey
- Downstream
- Length Surveyed
- 303.9 ft.
- Total Length
- 303.9 ft.
- Structural Index
- 3
- Structural Quick
- 423A
- Structural Rating
- 41
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 41
Pipe schematic from manhole 08 0054 to 08 0053 Observation photos (3)

0 ft. - Water Mark, 20 %of cross sectional area

7 ft. - General Observation - CHIPPING @ THE JOINT

12.5 ft. - Fracture Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES