Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 18, 2016, 07:03 AM
Date
03/18/2016
W/O
0557681
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00057
PipeID
P11467
Time
12:03 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6677
Sewer Name
J JOINT OUTFALL J - UNIT 1E
City
PALO VERDES
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
47
Purpose
Capital Improvement Program Assesment
Project
20160315MDM_JOINT_OUTFALL_J_UNIT_1E
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Upstream MH
J 0222
Downstream MH
J 0219
Dir. of Survey
Downstream
Length Surveyed
1385.6 ft.
Total Length
1385.6 ft.
Structural Index
3
Structural Quick
5E4F
Structural Rating
1550
O&M Index
2
O&M Quick
2p00
O&M Rating
488
Overall Index
2
Overall Quick
Overall Rating
2038
Pipe schematic from manhole J 0222 to J 0219
MH: J 0222MH: J 0219downstream0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MGO - General Observation - MH CONN 9:00 OPEN0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 2:10AM2 ft. SSS - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Start - SWOLLEN BLISTEWRING LAITANCE COAT17.9 ft. SSS - Surface Spalling, from 02 to 05 o'clock, within 8 inches of joint: YES - BLISTERING LAITANCE COAT42.1 ft. SSS - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES - PEELING LAITANCE COAT66.4 ft. SSS - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES - PEELING LAITANCE COAT79.3 ft. SSS - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES91.2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES - SEVERE AGG91.2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG97.8 ft. SRV - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: YES - CIRCUM REBAR100.9 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, - CIRCUM REBAR125.6 ft. SRV - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR129.2 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish132.9 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES, Start - LONG REBAR137.5 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES, Finish138.8 ft. SRV - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: YES - CIRCUM REBAR141.9 ft. SAM - Surface Aggregate Missing, from 10 to 12 o'clock, within 8 inches of joint: YES - SEVERE AGG163.4 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR164.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start168 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES - LONG REBAR171.1 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES178.3 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG178.3 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG179.6 ft. MGP - General Photograph187 ft. SRV - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: YES - CIRCUM REBAR207.8 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR210.5 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES, Start - LONG218.4 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish223.8 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES, Finish227.4 ft. SRV - Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: NO230.6 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES - LONG234.5 ft. SRV - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: YES - LONG CIRCUM281 ft. SRV - Surface Reinforcement Visible, from 10 to 12 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR285.7 ft. MGP - General Photograph290.6 ft. SRV - Surface Reinforcement Visible, from 10 to 12 o'clock, within 8 inches of joint: YES, Finish340.2 ft. SRV - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: YES - CIRCUM REBAR348.7 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC348.7 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish354.6 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES - SEVERE AGG363.1 ft. SRV - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: YES - CIRCUM409.7 ft. SAP - Surface Aggregate Projecting, from 08 to 11 o'clock, within 8 inches of joint: YES - SEVERE426 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES - CIRCUM545.3 ft. SSS - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES631.9 ft. SSS - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES700.9 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES - SEVERE AGG SPORATIC700.9 ft. SSS - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES848 ft. SSS - Surface Spalling, from 01 to 05 o'clock, within 8 inches of joint: YES - PEELING LAITANCE COAT856.3 ft. SSS - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES881.6 ft. SRV - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: YES - CIRCUM REBAR1067.1 ft. SSS - Surface Spalling, from 12 to 05 o'clock, within 8 inches of joint: YES - PEELING LAITANCE COAT1067.1 ft. MGP - General Photograph1161.6 ft. SSS - Surface Spalling, from 08 to 11 o'clock, within 8 inches of joint: YES - PEELING CONCRETE1250.4 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO - LONG REBAR1356.4 ft. SRV - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - CIRCUM REBAR1370.9 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR1385.3 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG SPORATIC1385.3 ft. MGO - General Observation - MH CONN OPEN STOPLOG IN PLACE 3:001385.3 ft. SSS - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish - PEELING SWOLLEN BLISTERING LAITANCE COAT1385.3 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR1385.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish1385.6 ft. AMH - Downstream Manhole, Survey Ends - 5:10AM

Observation photos (48)

  • Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Start - SWOLLEN BLISTEWRING LAITANCE COAT

    2 ft. - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Start - SWOLLEN BLISTEWRING LAITANCE COAT

  • Surface Spalling, from 02 to 05 o'clock, within 8 inches of joint: YES - BLISTERING LAITANCE COAT

    17.9 ft. - Surface Spalling, from 02 to 05 o'clock, within 8 inches of joint: YES - BLISTERING LAITANCE COAT

  • Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES - PEELING LAITANCE COAT

    42.1 ft. - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES - PEELING LAITANCE COAT

  • Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES - PEELING LAITANCE COAT

    66.4 ft. - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES - PEELING LAITANCE COAT

  • Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES

    79.3 ft. - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES - SEVERE AGG

    91.2 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES - SEVERE AGG

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    91.2 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    97.8 ft. - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES,  - CIRCUM REBAR

    100.9 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, - CIRCUM REBAR

  • Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    125.6 ft. - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES, Start - LONG REBAR

    132.9 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES, Start - LONG REBAR

  • Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES, Finish

    137.5 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES, Finish

  • Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    138.8 ft. - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

  • Surface Aggregate Missing, from 10 to 12 o'clock, within 8 inches of joint: YES - SEVERE AGG

    141.9 ft. - Surface Aggregate Missing, from 10 to 12 o'clock, within 8 inches of joint: YES - SEVERE AGG

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR

    163.4 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    164.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES - LONG REBAR

    168 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES - LONG REBAR

  • Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES

    171.1 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    178.3 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • General Photograph

    179.6 ft. - General Photograph

  • Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    187 ft. - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    207.8 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES, Start - LONG

    210.5 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES, Start - LONG

  • Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: NO

    227.4 ft. - Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES - LONG

    230.6 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES - LONG

  • Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: YES - LONG CIRCUM

    234.5 ft. - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: YES - LONG CIRCUM

  • Surface Reinforcement Visible, from 10 to 12 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR

    281 ft. - Surface Reinforcement Visible, from 10 to 12 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR

  • General Photograph

    285.7 ft. - General Photograph

  • Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    340.2 ft. - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

    348.7 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES - SEVERE AGG

    354.6 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES - SEVERE AGG

  • Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: YES - CIRCUM

    363.1 ft. - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: YES - CIRCUM

  • Surface Aggregate Projecting, from 08 to 11 o'clock, within 8 inches of joint: YES - SEVERE

    409.7 ft. - Surface Aggregate Projecting, from 08 to 11 o'clock, within 8 inches of joint: YES - SEVERE

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES - CIRCUM

    426 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES - CIRCUM

  • Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES

    545.3 ft. - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES

  • Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES

    631.9 ft. - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES - SEVERE AGG SPORATIC

    700.9 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES - SEVERE AGG SPORATIC

  • Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES

    700.9 ft. - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES

  • Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES

    856.3 ft. - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    881.6 ft. - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

  • Surface Spalling, from 12 to 05 o'clock, within 8 inches of joint: YES - PEELING LAITANCE COAT

    1067.1 ft. - Surface Spalling, from 12 to 05 o'clock, within 8 inches of joint: YES - PEELING LAITANCE COAT

  • General Photograph

    1067.1 ft. - General Photograph

  • Surface Spalling, from 08 to 11 o'clock, within 8 inches of joint: YES - PEELING CONCRETE

    1161.6 ft. - Surface Spalling, from 08 to 11 o'clock, within 8 inches of joint: YES - PEELING CONCRETE

  • Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO - LONG REBAR

    1250.4 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO - LONG REBAR

  • Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    1356.4 ft. - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    1370.9 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG SPORATIC

    1385.3 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG SPORATIC

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR

    1385.3 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR

Observations (63)

DistanceCodeObservation
354.6SAVSEVERE AGG
132.9SRVLONG REBAR
631.9SSS
100.9SRVCIRCUM REBAR
207.8SRVCIRCUM REBAR
700.9SAVSEVERE AGG SPORATIC
0MWM
409.7SAPSEVERE
1385.3SAVSEVERE AGG SPORATIC
1370.9SRVCIRCUM REBAR
1250.4SRVLONG REBAR
1385.3MGOMH CONN OPEN STOPLOG IN PLACE 3:00
1067.1SSSPEELING LAITANCE COAT
137.5SRV
1385.6AMH5:10AM
230.6SRVLONG
178.3SAMSEVERE AGG
129.2SRV
218.4SRV
187SRVCIRCUM REBAR
285.7MGP
1161.6SSSPEELING CONCRETE
42.1SSSPEELING LAITANCE COAT
281SRVLONG CIRCUM REBAR
91.2SAVSEVERE AGG
171.1SRV
17.9SSSBLISTERING LAITANCE COAT
340.2SRVCIRCUM REBAR
1385.3SSSPEELING SWOLLEN BLISTERING LAITANCE COAT
1385.3SRVCIRCUM REBAR
179.6MGP
290.6SRV
881.6SRVCIRCUM REBAR
426SRVCIRCUM
141.9SAMSEVERE AGG
2SSSSWOLLEN BLISTEWRING LAITANCE COAT
0MGOMH CONN 9:00 OPEN
234.5SRVLONG CIRCUM
0MWL
79.3SSS
348.7SAVSEVERE AGG SPORATIC
1356.4SRVCIRCUM REBAR
227.4SRV
856.3SSS
1067.1MGP
163.4SRVLONG CIRCUM REBAR
0AMH2:10AM
700.9SSS
138.8SRVCIRCUM REBAR
348.7SAM
363.1SRVCIRCUM
168SRVLONG REBAR
1385.3DAGS
66.4SSSPEELING LAITANCE COAT
178.3SAVSEVERE AGG
91.2SAVSEVERE AGG
164.1DAGS
848SSSPEELING LAITANCE COAT
210.5SRVLONG
97.8SRVCIRCUM REBAR
125.6SRVCIRCUM REBAR
545.3SSS
223.8SRV

Properties (4)

custom_field_three
LONG CIRCUM REBAR
custom_field_two
2
customer
LACSD
datetime
2016-03-18T00:03:06-07:00