Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 15, 2016, 03:26 PM
  • C 0485_C 0484_3152016_090200.mp4

Date
03/15/2016
W/O
0547102
Weather
Dry
Operator/Surveyor
MIRANDA
Sewer ID
Z00132
PipeID
P09735
Time
8:26 AM
Certificate
U-1014-06022542
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0093
Sewer Name
C JOINT OUTFALL C - UNIT 6C RENOVATION*
City
LAKEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
13
Purpose
Routine Assessment
Project
20160315AM_JOINT_OUTFALL_C_UNIT_6C_RENOVATION
Material
Vitrified Clay Pipe
Shape
Circular
Height
30 in.
Upstream MH
C 0485
Downstream MH
C 0484
Dir. of Survey
Downstream
Length Surveyed
476.8 ft.
Total Length
476.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
3122
O&M Rating
7
Overall Index
2
Overall Quick
Overall Rating
7
Pipe schematic from manhole C 0485 to C 0484
MH: C 0485MH: C 0484downstream0 ft. MGO - General Observation - ACTIVE CONN. INSIDE THE MH. @ 03 O'CLOCK0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 9:01 AM37.7 ft. MGO - General Observation - JOINT MATERIAL PEELING/FLAKING, START62.4 ft. MGO - General Observation - JOINT MATERIAL PEELING/FLAKING, FINISH158.8 ft. TBI - Tap Break-In Intruding, at 03 o'clock, -, -, within 8 inches of joint: NO, 4", 1"- 2" - ACTIVE241.2 ft. TBD - Tap Break-In Defective, at 10 o'clock, -, , within 8 inches of joint: NO, 4" - ACTIVE275.5 ft. TBI - Tap Break-In Intruding, at 10 o'clock, -, -, within 8 inches of joint: NO, 4", 1"- 2" - OPEN475.5 ft. MGO - General Observation - SLIGHT GREASE THROUGHOUT THE REACH476.8 ft. AMH - Downstream Manhole, Survey Ends - 9:23 AM

Observation photos (5)

  • General Observation - JOINT MATERIAL PEELING/FLAKING, START

    37.7 ft. - General Observation - JOINT MATERIAL PEELING/FLAKING, START

  • General Observation - JOINT MATERIAL PEELING/FLAKING, FINISH

    62.4 ft. - General Observation - JOINT MATERIAL PEELING/FLAKING, FINISH

  • Tap Break-In Intruding, at 03 o'clock, -, -, within 8 inches of joint: NO, 4", 1"- 2" - ACTIVE

    158.8 ft. - Tap Break-In Intruding, at 03 o'clock, -, -, within 8 inches of joint: NO, 4", 1"- 2" - ACTIVE

  • Tap Break-In Defective, at 10 o'clock, -,  , within 8 inches of joint: NO, 4" - ACTIVE

    241.2 ft. - Tap Break-In Defective, at 10 o'clock, -, , within 8 inches of joint: NO, 4" - ACTIVE

  • Tap Break-In Intruding, at 10 o'clock, -, -, within 8 inches of joint: NO, 4", 1"- 2" - OPEN

    275.5 ft. - Tap Break-In Intruding, at 10 o'clock, -, -, within 8 inches of joint: NO, 4", 1"- 2" - OPEN

Observations (11)

DistanceCodeObservation
0MGOACTIVE CONN. INSIDE THE MH. @ 03 O'CLOCK
37.7MGOJOINT MATERIAL PEELING/FLAKING, START
0MWM
0MWL
158.8TBIACTIVE
62.4MGOJOINT MATERIAL PEELING/FLAKING, FINISH
241.2TBDACTIVE
475.5MGOSLIGHT GREASE THROUGHOUT THE REACH
275.5TBIOPEN
0AMH9:01 AM
476.8AMH9:23 AM

Properties (3)

custom_field_two
4
customer
LACSD
datetime
2016-03-15T08:26:29-07:00