Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 11, 2016, 11:38 AM
  • A 0525_A 0524_3112016_044441.mp4

Date
03/11/2016
W/O
0552352
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00315
PipeID
P20206
Time
3:38 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0090
Sewer Name
A JOA-1A DISTRICT 5 INTERCEPTOR
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
20
Purpose
Capital Improvement Program Assesment
Project
20160311MDM_JOA_1A_DISTRICT_5_INTERCEPTOR
Material
Reinforced Concrete Pipe
Shape
Rectangular
Height
0 in.
Upstream MH
A 0525
Downstream MH
A 0524
Dir. of Survey
Downstream
Length Surveyed
11.8 ft.
Total Length
11.8 ft.
Structural Index
4
Structural Quick
5131
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
8
Pipe schematic from manhole A 0525 to A 0524
MH: A 0525MH: A 0524downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:35AM0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. SAP - Surface Aggregate Projecting, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. MGO - General Observation - MAG COAT 50% START8 ft. SRV - Surface Reinforcement Visible, at 01 o'clock, within 8 inches of joint: NO - POSSIBLE SURFACE REBAR11.3 ft. MGO - General Observation - MAG COAT 50% FINISH11.3 ft. SAP - Surface Aggregate Projecting, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG11.8 ft. AMH - Downstream Manhole, Survey Ends - 4:50AM

Observation photos (2)

  • Surface Aggregate Projecting, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Projecting, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Reinforcement Visible, at 01 o'clock, within 8 inches of joint: NO - POSSIBLE SURFACE REBAR

    8 ft. - Surface Reinforcement Visible, at 01 o'clock, within 8 inches of joint: NO - POSSIBLE SURFACE REBAR

Observations (9)

DistanceCodeObservation
2SAPSEVERE AGG
11.3MGOMAG COAT 50% FINISH
0MWM
0AMH4:35AM
11.3SAPSEVERE AGG
8SRVPOSSIBLE SURFACE REBAR
2MGOMAG COAT 50% START
0MWL
11.8AMH4:50AM

Properties (4)

custom_field_three
PROJECTING SEVERE AGG -1 POSSIBLE REBAR
custom_field_two
3
customer
LACSD
datetime
2016-03-11T03:38:47-08:00