Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 4, 2016, 09:31 AM
  • 02 1358_02 1357_342016_014735.mp4

Date
03/04/2016
W/O
0541751
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00277
PipeID
P03881
Time
1:31 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0080
Sewer Name
02 JANE STREET BRANCH TRUNK
City
LOS ANGLES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
11A
Purpose
Routine Assessment
Project
20160302MDM_JANE_STREET_BRANCH_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
02 1357
Downstream MH
02 1358
Dir. of Survey
Upstream
Length Surveyed
355.7 ft.
Total Length
355.7 ft.
Structural Index
2
Structural Quick
3A2B
Structural Rating
62
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
68
Pipe schematic from manhole 02 1357 to 02 1358
MH: 02 1357MH: 02 1358upstream0 ft. AMH - Upstream Manhole, Survey Ends - 2:55AM0.2 ft. MGO - General Observation - LNG PIPE IN MH0.2 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - 80% AT JOINTS0.2 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Finish - 20% AT JOINTS2.4 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - SLIGHT32.9 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, - H73.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open76.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped81.8 ft. TBI - Tap Break-In Intruding, at 12 o'clock, -, -, within 8 inches of joint: YES, 6", 1", 6" - Open 1" INTRUDING83.8 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SLIGHT93 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Finish - H93 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Finish - H96.2 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start - H102.6 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Start - H121.7 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - H132.4 ft. MWM - Water Mark, 30 %of cross sectional area141.9 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Finish - H146.1 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Start - H167.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"171 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"196.3 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Finish - H196.3 ft. MWM - Water Mark, 50 %of cross sectional area196.3 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Finish - H205 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Start - H205 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start - H229.8 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - SLIGHT235.9 ft. MWM - Water Mark, 30 %of cross sectional area235.9 ft. FS - Fracture Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES, Finish - H235.9 ft. FS - Fracture Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES, Finish - H235.9 ft. MGP - General Photograph - 12" VCP252.2 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SLIGHT270.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"272.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open283.8 ft. FS - Fracture Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES, Start - H283.8 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SLIGHT285.2 ft. FS - Fracture Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES, Start - H296.2 ft. FS - Fracture Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES, Finish - H296.2 ft. FS - Fracture Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES, Finish - H302.4 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SLIGHT314.8 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS314.8 ft. FL - Fracture Longitudinal, at 09 TO 03 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS323.6 ft. FS - Fracture Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES, Start - H324.1 ft. FS - Fracture Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES, Start - H326.8 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - H330.1 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SLIGHT336.2 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - H338.6 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - H338.8 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - H342.3 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - HAIRLINE347.1 ft. MGO - General Observation - 12" VCP355.7 ft. MWM - Water Mark, 40 %of cross sectional area355.7 ft. AMH - Downstream Manhole, Survey Begins - 1:40AM355.7 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (6)

  • General Observation - 12" VCP

    8.6 ft. - General Observation - 12" VCP

  • Fracture Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES, Start - H

    31.6 ft. - Fracture Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES, Start - H

  • Fracture Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES, Start - H

    32.1 ft. - Fracture Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES, Start - H

  • Fracture Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES, Start - H

    71.9 ft. - Fracture Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES, Start - H

  • General Photograph - 12" VCP

    119.8 ft. - General Photograph - 12" VCP

  • General Observation - LNG PIPE IN MH

    355.5 ft. - General Observation - LNG PIPE IN MH

Observations (53)

DistanceCodeObservation
353.3FCSLIGHT
31.6FSH
159.4FLH
125.9FCSLIGHT
103.5FCSLIGHT
28.9FCH
84.8TFC
259.5FLH
159.4MWM
32.1FSH
234FLH
0MWM
355.5MGOLNG PIPE IN MH
59.5FSH
355.5FC80% AT JOINTS
19.5FCH
71.9FSH
184.7TFC
119.8MWM
213.8FLH
278.8TFCCapped
262.7FLH
119.8FSH
322.8FLH
53.3FCSLIGHT
150.7FLH
271.9FCSLIGHT
223.3MWM
59.5FSH
0AMH1:40AM
25.6FCSLIGHT
71.9FCSLIGHT
159.4FLH
13.4FCHAIRLINE
16.9FCH
150.7FLH
40.9FCHAIRLINE AT JOINTS
273.9TBIOpen 1" INTRUDING
17.1FCH
355.7AMH2:55AM
119.8FSH
70.5FSH
253.1FLH
355.5FL20% AT JOINTS
83.4TFOpen
40.9FLHAIRLINE AT JOINTS
209.6FLH
262.7FLH
0MWL
282.3TFOpen
8.6MGO12" VCP
119.8MGP12" VCP
188.1TFC

Properties (4)

custom_field_three
HAIRLINE SPRIAL JOINT TO JOINT LONGER
custom_field_two
2
customer
LACSD
datetime
2016-03-04T01:31:35-08:00