Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 2, 2016, 10:30 AM
  • 15 0773_15 0772_322016_023349.mp4

Date
03/02/2016
W/O
0552373
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00593
PipeID
P12974
Time
2:30 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Jetting
Media Label
H0077
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 2&5
City
ARCADIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
04
Purpose
Capital Improvement Program Assesment
Project
20160302MDM_ARCADIA_SIERRA_MADRE_TRUNK_SECTS_2_5
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
15 0773
Downstream MH
15 0772
Dir. of Survey
Downstream
Length Surveyed
402.7 ft.
Total Length
402.7 ft.
Structural Index
3
Structural Quick
4522
Structural Rating
24
O&M Index
4
O&M Quick
4321
O&M Rating
14
Overall Index
3
Overall Quick
Overall Rating
38
Pipe schematic from manhole 15 0773 to 15 0772
MH: 15 0773MH: 15 0772downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 2:20AM0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE8 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG9.4 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE15.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open21.4 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG82 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"131.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"133.5 ft. MGP - General Photograph133.5 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN -99% ROOTS133.5 ft. RBC - Roots Ball Connection, from 08 to 04 o'clock, 60 %, within 8 inches of joint: YES142.9 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES - SEVERE AGG272.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped274.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"323.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Active325.4 ft. RBJ - Roots Ball Joint, from 07 to 05 o'clock, 90 %, within 8 inches of joint: YESR325.4 ft. MGP - General Photograph362.4 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG402.4 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active402.4 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active402.4 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - PEELING CONCRETE402.4 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG402.7 ft. AMH - Downstream Manhole, Survey Ends - 3:10AM

Observation photos (11)

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    0 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

    8 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

    9.4 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

    21.4 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • General Photograph

    133.5 ft. - General Photograph

  • Roots Ball Connection, from 08 to 04 o'clock, 60 %, within 8 inches of joint: YES

    133.5 ft. - Roots Ball Connection, from 08 to 04 o'clock, 60 %, within 8 inches of joint: YES

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES - SEVERE AGG

    142.9 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES - SEVERE AGG

  • Roots Ball Joint, from 07 to 05 o'clock, 90 %, within 8 inches of joint: YESR

    325.4 ft. - Roots Ball Joint, from 07 to 05 o'clock, 90 %, within 8 inches of joint: YESR

  • General Photograph

    325.4 ft. - General Photograph

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

    362.4 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

Observations (27)

DistanceCodeObservation
82TFC
133.5MGP
133.5TFDOPEN -99% ROOTS
133.5RBC
274.3TFC
402.4MGOConn. @ Mh, 9 O' Clock. Active
0MWL
0MWM
15.3TFOpen
2SSSPEELING CONCRETE
402.4MGOConn. @ Mh, 3 O' Clock. Active
402.4SSSPEELING CONCRETE
402.7AMH3:10AM
0AMH2:20AM
362.4SAMSEVERE AGG
0MGOConn. @ Mh, 3 O' Clock. Active
131.8TFC
142.9SAMSEVERE AGG
8SAMSEVERE AGG
325.4RBJ
272.1TFCCapped
9.4SSSPEELING CONCRETE
325.4MGP
0SAMSEVERE AGG
323.6TFActive
402.4SAMSEVERE AGG
21.4SAMSEVERE AGG

Properties (4)

custom_field_three
MISSING SEVERE AGG -PEELING CONCRETE
custom_field_two
2
customer
LACSD
datetime
2016-03-02T02:30:06-08:00