- Date
- 02/11/2016
- W/O
- 0556813
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00325
- PipeID
- P08218
- Time
- 12:34 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- H0049
- Sewer Name
- A JOA-1A SAN JOSE CREEK WRP INTERCEPTOR
- City
- EL MONTE
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 15
- Page No.
- 29
- Purpose
- Routine Assessment
- Project
- 20160211MDM_JOA_1A_SAN_JOSE_CREEK_WRP_INTERCEPTOR
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 63 in.
- Upstream MH
- A 0307
- Downstream MH
- A 0308
- Dir. of Survey
- Upstream
- Length Surveyed
- 6.9 ft.
- Total Length
- 6.9 ft.
- Structural Index
- 2
- Structural Quick
- 2100
- Structural Rating
- 2
- O&M Index
- 4
- O&M Quick
- 4100
- O&M Rating
- 4
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 6
Pipe schematic from manhole A 0307 to A 0308 Observation photos (5)

0 ft. - Water Mark, 60 %of cross sectional area

2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - PEELING BLISTERING CONCRETE

4 ft. - General Observation - HANGING MASTIC

6 ft. - General Observation - PEELING MASTIC JOINT EXPOSED

6.9 ft. - Survey Abandoned - UPLEG DOWNSTREAM SIPHON