Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 8, 2016, 08:35 AM
  • 18 0036_18 0453_282016_012546.mp4

Date
02/08/2016
W/O
0547024
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00691
PipeID
P14305
Time
12:35 AM
Certificate
U-1014-06022254
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0044
Sewer Name
18 NORTH PLANT OUTFALL TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
14
Purpose
Capital Improvement Program Assesment
Project
20160205MDM_NORTH_PLANT_OUTFALL_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Upstream MH
18 0453
Downstream MH
18 0036
Dir. of Survey
Upstream
Length Surveyed
13 ft.
Total Length
13 ft.
Structural Index
2
Structural Quick
3224
Structural Rating
14
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
18
Pipe schematic from manhole 18 0453 to 18 0036
MH: 18 0453MH: 18 0036upstream0 ft. AMH - Upstream Manhole, Survey Ends - 1:40AM0.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - SLIGHT0.9 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - SLIGHT2.1 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - HAIRLINE4.3 ft. FC - Fracture Circumferential, from 11 to 12 o'clock, within 8 inches of joint: YES - HAIRLINE5 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - HAIRLINE6.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT7 ft. FC - Fracture Circumferential, from 02 to 05 o'clock, within 8 inches of joint: YES - SLIGHT13 ft. MWM - Water Mark, 50 %of cross sectional area13 ft. AMH - Downstream Manhole, Survey Begins - 1:25AM13 ft. MWL - Water Level, 5 %of cross sectional area - STOPLOG IN PLACE UPSTREAM

Observation photos (3)

  • Water Level, 5 %of cross sectional area - STOPLOG IN PLACE UPSTREAM

    0 ft. - Water Level, 5 %of cross sectional area - STOPLOG IN PLACE UPSTREAM

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

    6.9 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

  • Upstream Manhole, Survey Ends - 1:40AM

    13 ft. - Upstream Manhole, Survey Ends - 1:40AM

Observations (11)

DistanceCodeObservation
6.9FLSLIGHT
6FCSLIGHT
0MWM
12.1FCSLIGHT
8FLHAIRLINE
13AMH1:40AM
10.9FCHAIRLINE
12.7FLSLIGHT
0AMH1:25AM
0MWLSTOPLOG IN PLACE UPSTREAM
8.7FCHAIRLINE

Properties (4)

custom_field_three
LONG SLIGHT FRACTURE JOINT TO JOINT LONGER
custom_field_two
2
customer
LACSD
datetime
2016-02-08T00:35:31-08:00