Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 13, 2016, 10:07 AM
Date
01/13/2016
W/O
0536420
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00362
PipeID
P04750
Time
2:07 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0013
Sewer Name
C JOINT OUTFALL C - UNIT 4D
City
LAKEWOOD
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
08
Purpose
Capital Improvement Program Assesment
Project
20160112MDM_JOINT_OUTFALL_C_UNIT_4D
Material
Vitrified Clay Pipe
Shape
Circular
Height
27 in.
Upstream MH
C 0566
Downstream MH
C 0565
Dir. of Survey
Downstream
Length Surveyed
420.9 ft.
Total Length
420.9 ft.
Structural Index
3
Structural Quick
3724
Structural Rating
29
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
31
Pipe schematic from manhole C 0566 to C 0565
MH: C 0566MH: C 0565downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - MH CONN OPEN 9:000 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 2:50AM23.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start27.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT27.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish62.3 ft. DSZ - Deposits Settled Other, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES - ROCKS62.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SLIGHT101.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - SLIGHT117.9 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES130.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE142.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - H171.5 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES226.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - HAIRLINE234.8 ft. FS - Fracture Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES, Start - HAIRLINE239.3 ft. FS - Fracture Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES, Finish - H267.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE278 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - H313.9 ft. MGO - General Observation - SWOLLEN JOINT FILLER329.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Active367.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H380.1 ft. FC - Fracture Circumferential, from 11 to 12 o'clock, within 8 inches of joint: YES - H394.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - H420.9 ft. AMH - Downstream Manhole, Survey Ends - 3:40AM

Observation photos (8)

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

    27.1 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SLIGHT

    62.3 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - SLIGHT

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

    130.7 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - HAIRLINE

    226.7 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - HAIRLINE

  • Fracture Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

    234.8 ft. - Fracture Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

    267.1 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - HAIRLINE

  • General Observation - SWOLLEN JOINT FILLER

    313.9 ft. - General Observation - SWOLLEN JOINT FILLER

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H

    367.5 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H

Observations (26)

DistanceCodeObservation
0MWL
313.9MGOSWOLLEN JOINT FILLER
101.9FLSLIGHT
329.9TFActive
142.3FLH
23.1CL
234.8FSHAIRLINE
62.3DSZROCKS
0MGOMH CONN OPEN 9:00
420.9AMH3:40AM
278FLH
380.1FCH
394.8FLH
367.5FLH
117.9CL
171.5CL
226.7FLHAIRLINE
130.7FLHAIRLINE
62.3FLSLIGHT
0MGOConn. @ Mh, 3 O' Clock. Active
0MWM
267.1FLHAIRLINE
27.1FLSLIGHT
239.3FSH
27.1CL
0AMH2:50AM

Properties (4)

custom_field_three
SLIGHT LONG FRACTURE JOINT TO JOINT LONGER
custom_field_two
2
customer
LACSD
datetime
2016-01-13T02:07:46-08:00