Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 8, 2016, 05:00 PM
  • A 0847_A 0846_182016_093958.mp4

Date
01/08/2016
W/O
0547112
Weather
Dry
Operator/Surveyor
MIRANDA
Sewer ID
Z00324
PipeID
P08187
Time
9:00 AM
Certificate
U-1014-06022542
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7036
Sewer Name
A JOA-1A NORTH LONG BEACH INTERCEPTOR
City
LAKEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
08
Purpose
Routine Assessment
Project
20160108AM_JOA_1A_NORTH_LONG_BEACH_INTERCEPTOR
Material
Vitrified Clay Pipe
Shape
Circular
Height
33 in.
Upstream MH
A 0847
Downstream MH
A 0846
Dir. of Survey
Downstream
Length Surveyed
750.6 ft.
Total Length
750.6 ft.
Structural Index
2
Structural Quick
4135
Structural Rating
56
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
60
Pipe schematic from manhole A 0847 to A 0846
MH: A 0847MH: A 0846downstream0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MWM - Water Mark, 55 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 9:30 AM49.6 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start59.4 ft. CM - Crack Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES59.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish99 ft. CC - Crack Circumferential, from 12 to 01 o'clock, within 8 inches of joint: YES104.6 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES289.9 ft. CC - Crack Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES452.1 ft. MGO - General Observation - JOINT MATERIAL, POSSIBLE CONCRETE, 5%497.2 ft. MMC - Material Change, Other (state in comments) - CONCRETE PIPE497.2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES497.2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES499.4 ft. MMC - Material Change, Vitrified clay pipe534.5 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES539.7 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES, Start539.7 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES547.1 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES, Finish547.1 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start547.1 ft. FM - Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES547.1 ft. CS - Crack Spiral, from 10 to 11 o'clock, within 8 inches of joint: YES547.3 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start552.1 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES552.1 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Finish552.8 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Finish552.8 ft. CS - Crack Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES558.6 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start558.6 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start558.6 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES564.9 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Finish564.9 ft. FS - Fracture Spiral, from 09 to 10 o'clock, within 8 inches of joint: YES, Start564.9 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish570.8 ft. FS - Fracture Spiral, from 09 to 10 o'clock, within 8 inches of joint: YES, Finish593.3 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES, Start600.1 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES600.1 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES, Finish600.6 ft. CC - Crack Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES600.6 ft. FS - Fracture Spiral, from 12 to 01 o'clock, within 8 inches of joint: YES606.7 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start606.7 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Start631.1 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Finish631.1 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Finish750.1 ft. MGO - General Observation - CONTINUOUS CRACKS THROUGHOUT THE REACH750.6 ft. AMH - Downstream Manhole, Survey Ends - 10:42 AM

Observation photos (11)

  • Water Level, 30 %of cross sectional area

    0 ft. - Water Level, 30 %of cross sectional area

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    104.6 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • General Observation - JOINT MATERIAL, POSSIBLE CONCRETE, 5%

    452.1 ft. - General Observation - JOINT MATERIAL, POSSIBLE CONCRETE, 5%

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES

    497.2 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES

    497.2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES, Start

    539.7 ft. - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

    547.1 ft. - Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    552.1 ft. - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES

    552.8 ft. - Crack Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 09 to 10 o'clock, within 8 inches of joint: YES, Start

    564.9 ft. - Fracture Spiral, from 09 to 10 o'clock, within 8 inches of joint: YES, Start

  • Fracture Spiral, from 12 to 01 o'clock, within 8 inches of joint: YES

    600.6 ft. - Fracture Spiral, from 12 to 01 o'clock, within 8 inches of joint: YES

Observations (44)

DistanceCodeObservation
600.1CL
534.5CL
497.2MMCCONCRETE PIPE
631.1CL
49.6CL
606.7CL
99CC
539.7CL
600.6CC
631.1CL
750.6AMH10:42 AM
452.1MGOJOINT MATERIAL, POSSIBLE CONCRETE, 5%
547.3CL
499.4MMC
552.1FL
59.4CM
558.6CL
558.6CL
570.8FS
552.8CL
104.6CL
750.1MGOCONTINUOUS CRACKS THROUGHOUT THE REACH
547.1CL
552.8CS
539.7CL
606.7CL
552.1CL
564.9CL
593.3CL
564.9FS
600.1CL
547.1CL
547.1FM
0MWL
564.9CL
558.6CL
600.6FS
497.2SAV
497.2SSS
59.4CL
0MWM
547.1CS
0AMH9:30 AM
289.9CC

Properties (4)

custom_field_three
CONTINUOUS CRACKS THROUGHOUT
custom_field_two
2
customer
LACSD
datetime
2016-01-08T09:00:19-08:00