- Date
- 01/04/2016
- W/O
- 0546885
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00158
- PipeID
- P23006
- Time
- 1:45 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- G6667
- Sewer Name
- D JOINT OUTFALL D - UNIT 7
- City
- CARSON
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 08
- Page No.
- 13
- Purpose
- Capital Improvement Program Assesment
- Project
- 20160104MDM_JOINT_OUTFALL_D_UNIY_7
- Material
- RCP-CTL
- Shape
- Circular
- Height
- 60 in.
- Upstream MH
- D JOINT
- Downstream MH
- D 0227
- Dir. of Survey
- Downstream
- Length Surveyed
- 6.4 ft.
- Total Length
- 6.4 ft.
- Structural Index
- 5
- Structural Quick
- 5442
- Structural Rating
- 28
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 5
- Overall Quick
- —
- Overall Rating
- 28
Pipe schematic from manhole D JOINT to D 0227 Observation photos (4)

2 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - LONG REBAR

2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

2 ft. - General Observation - MAG COAT10% START

2 ft. - General Observation - MISSING TILES 90% START