Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 8, 2016, 07:34 PM
  • 03 0264_03 0263A_1182016_114720.mp4

Date
11/08/2016
W/O
0602283
Weather
Very Dry
Operator/Surveyor
MIRANDA
Sewer ID
Z00385
PipeID
P04866
Time
11:34 AM
Certificate
U-1014-06022542
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7268
Sewer Name
03 MARKET STREET TRUNK
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
07
Purpose
Routine Assessment
Project
20161108AM_MARKET_STREET_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Upstream MH
03 0264
Downstream MH
03 0263A
Dir. of Survey
Downstream
Length Surveyed
350.4 ft.
Total Length
350.4 ft.
Structural Index
3
Structural Quick
413A
Structural Rating
43
O&M Index
2
O&M Quick
2600
O&M Rating
12
Overall Index
3
Overall Quick
Overall Rating
55
Pipe schematic from manhole 03 0264 to 03 0263A
MH: 03 0264MH: 03 0263Adownstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 11:45 AM0 ft. MGO - General Observation - ROACHES INSIDE THE MH.5.1 ft. FM - Fracture Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES35.3 ft. TFI - Tap Factory Made Intruding, at 12 o'clock, -, -, within 8 inches of joint: YES, 6", 1" - ACTIVE51 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES71.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES74.6 ft. CM - Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES105 ft. TFI - Tap Factory Made Intruding, at 12 o'clock, -, -, within 8 inches of joint: YES, 6", 1" - ACTIVE135.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES168.1 ft. TFI - Tap Factory Made Intruding, at 12 o'clock, -, -, within 8 inches of joint: YES, 6", 1" - ACTIVE187.3 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES223.4 ft. CM - Crack Multiple, from 10 to 01 o'clock, within 8 inches of joint: YES227.7 ft. CM - Crack Multiple, from 10 to 01 o'clock, within 8 inches of joint: YES232.2 ft. TFI - Tap Factory Made Intruding, at 12 o'clock, -, -, within 8 inches of joint: YES, 6", 2" - ACTIVE242.6 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES250.9 ft. CM - Crack Multiple, from 11 to 02 o'clock, within 8 inches of joint: YES266.6 ft. CM - Crack Multiple, from 01 to 02 o'clock, within 8 inches of joint: YES279.2 ft. CM - Crack Multiple, from 10 to 12 o'clock, within 8 inches of joint: YES287.3 ft. TFI - Tap Factory Made Intruding, at 12 o'clock, -, -, within 8 inches of joint: YES, 6", 1" - ACTIVE302.4 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES314.4 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES343.4 ft. TFD - Tap Factory Made Defective, at 12 o'clock, -, within 8 inches of joint: YES, 6" - OPEN, CRACKED, PROTRUDING IN APPROX. 2"345.8 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN347.8 ft. MGO - General Observation - MULTIPLE CRACKS THROUGHOUT THE REACH348 ft. MGO - General Observation - SLIGHT GREASE/DEBRIS THROUGHOUT THE REACH348.4 ft. MGO - General Observation - ACTIVE CONN. INSIDE THE MH. @ 09 O'CLOCK348.4 ft. MGO - General Observation - ROACHES INSIDE THE MH.350.4 ft. AMH - Downstream Manhole, Survey Ends - 12:17 PM

Observation photos (11)

  • Fracture Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES

    5.1 ft. - Fracture Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES

  • Tap Factory Made Intruding, at 12 o'clock, -, -, within 8 inches of joint: YES, 6", 1" - ACTIVE

    35.3 ft. - Tap Factory Made Intruding, at 12 o'clock, -, -, within 8 inches of joint: YES, 6", 1" - ACTIVE

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    71.6 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Tap Factory Made Intruding, at 12 o'clock, -, -, within 8 inches of joint: YES, 6", 1" - ACTIVE

    105 ft. - Tap Factory Made Intruding, at 12 o'clock, -, -, within 8 inches of joint: YES, 6", 1" - ACTIVE

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    135.3 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Tap Factory Made Intruding, at 12 o'clock, -, -, within 8 inches of joint: YES, 6", 1" - ACTIVE

    168.1 ft. - Tap Factory Made Intruding, at 12 o'clock, -, -, within 8 inches of joint: YES, 6", 1" - ACTIVE

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    187.3 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Tap Factory Made Intruding, at 12 o'clock, -, -, within 8 inches of joint: YES, 6", 2" - ACTIVE

    232.2 ft. - Tap Factory Made Intruding, at 12 o'clock, -, -, within 8 inches of joint: YES, 6", 2" - ACTIVE

  • Tap Factory Made Intruding, at 12 o'clock, -, -, within 8 inches of joint: YES, 6", 1" - ACTIVE

    287.3 ft. - Tap Factory Made Intruding, at 12 o'clock, -, -, within 8 inches of joint: YES, 6", 1" - ACTIVE

  • Tap Factory Made Defective, at 12 o'clock, -, within 8 inches of joint: YES, 6" - OPEN, CRACKED, PROTRUDING IN APPROX. 2"

    343.4 ft. - Tap Factory Made Defective, at 12 o'clock, -, within 8 inches of joint: YES, 6" - OPEN, CRACKED, PROTRUDING IN APPROX. 2"

  • Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN

    345.8 ft. - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN

Observations (30)

DistanceCodeObservation
348MGOSLIGHT GREASE/DEBRIS THROUGHOUT THE REACH
250.9CM
348.4MGOACTIVE CONN. INSIDE THE MH. @ 09 O'CLOCK
105TFIACTIVE
227.7CM
314.4CL
242.6CL
135.3FL
232.2TFIACTIVE
279.2CM
0MWL
35.3TFIACTIVE
345.8FLPOSSIBLY BROKEN
0MWM
343.4TFDOPEN, CRACKED, PROTRUDING IN APPROX. 2"
302.4CM
287.3TFIACTIVE
51CM
74.6CM
168.1TFIACTIVE
71.6FL
5.1FM
0AMH11:45 AM
347.8MGOMULTIPLE CRACKS THROUGHOUT THE REACH
266.6CM
350.4AMH12:17 PM
348.4MGOROACHES INSIDE THE MH.
187.3CL
223.4CM
0MGOROACHES INSIDE THE MH.

Properties (4)

custom_field_three
POSSIBLE BROKEN PIPE, 345' D/S
custom_field_two
1
customer
LACSD
datetime
2016-11-08T11:34:44-08:00