Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 9, 2016, 09:31 PM
  • 03 0255A_03 0255_1192016_133855.mp4

Date
11/09/2016
W/O
0602283
Weather
Dry
Operator/Surveyor
DEVIN FRANKLIN
Sewer ID
Z00385
PipeID
P04858
Time
1:31 PM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7269
Sewer Name
03 MARKET STREET TRUNK
City
LONG_BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
07
Purpose
Routine Assessment
Project
20161104_DF_MARKET_STREET_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Upstream MH
03 0255A
Downstream MH
03 0255
Dir. of Survey
Downstream
Length Surveyed
297 ft.
Total Length
297 ft.
Structural Index
3
Structural Quick
5141
Structural Rating
27
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
29
Pipe schematic from manhole 03 0255A to 03 0255
MH: 03 0255AMH: 03 0255downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:34 PM0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0 ft. MGO - General Observation - ROACHES @ MH29.5 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"48.9 ft. MGO - General Observation - CHIPPING80.3 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6" - PROTRUDING 1 INCH106.8 ft. CM - Crack Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES115.2 ft. B - Broken, from 10 to 12 o'clock, within 8 inches of joint: YES119.7 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6" - PRTRUDING 1 INCH146.6 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES146.9 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES, Start149.9 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES, Finish159.4 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6" - PROTRUDING 1 INCH185 ft. CM - Crack Multiple, from 10 to 01 o'clock, within 8 inches of joint: YES197.1 ft. FM - Fracture Multiple, from 02 to 03 o'clock, within 8 inches of joint: YES201.9 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6" - PROTRUDING 1 INCH241.6 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"247.7 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start247.7 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES251.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish251.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start260.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish288.5 ft. TFD - Tap Factory Made Defective, at 12 o'clock, -, within 8 inches of joint: YES, 6", 6" - 90% ROOTS, ACTIVE294.8 ft. MGO - General Observation - GREASE THROUGHOUT THE REACH297 ft. AMH - Downstream Manhole, Survey Ends - 2:23 PM

Observation photos (14)

  • General Observation - CHIPPING

    48.9 ft. - General Observation - CHIPPING

  • Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6" - PROTRUDING 1 INCH

    80.3 ft. - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6" - PROTRUDING 1 INCH

  • Crack Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES

    106.8 ft. - Crack Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES

  • Broken, from 10 to 12 o'clock, within 8 inches of joint: YES

    115.2 ft. - Broken, from 10 to 12 o'clock, within 8 inches of joint: YES

  • Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6" - PRTRUDING 1 INCH

    119.7 ft. - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6" - PRTRUDING 1 INCH

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    146.6 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES, Finish

    149.9 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES, Finish

  • Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6" - PROTRUDING 1 INCH

    159.4 ft. - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6" - PROTRUDING 1 INCH

  • Crack Multiple, from 10 to 01 o'clock, within 8 inches of joint: YES

    185 ft. - Crack Multiple, from 10 to 01 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 02 to 03 o'clock, within 8 inches of joint: YES

    197.1 ft. - Fracture Multiple, from 02 to 03 o'clock, within 8 inches of joint: YES

  • Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6" - PROTRUDING 1 INCH

    201.9 ft. - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6" - PROTRUDING 1 INCH

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    247.7 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    251.7 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Tap Factory Made Defective, at 12 o'clock, -, within 8 inches of joint: YES, 6", 6" - 90% ROOTS, ACTIVE

    288.5 ft. - Tap Factory Made Defective, at 12 o'clock, -, within 8 inches of joint: YES, 6", 6" - 90% ROOTS, ACTIVE

Observations (27)

DistanceCodeObservation
288.5TFD90% ROOTS, ACTIVE
48.9MGOCHIPPING
0MWL
149.9CL
0AMH1:34 PM
106.8CM
0MWM
159.4TFAPROTRUDING 1 INCH
201.9TFAPROTRUDING 1 INCH
251.4CL
247.7CL
247.7CL
251.7FL
294.8MGOGREASE THROUGHOUT THE REACH
0MGOConn. @ Mh, 9 O' Clock. Active
119.7TFAPRTRUDING 1 INCH
80.3TFAPROTRUDING 1 INCH
0MGOROACHES @ MH
115.2B
29.5TFA
146.9CL
197.1FM
146.6CM
260.3FL
297AMH2:23 PM
241.6TFA
185CM

Properties (4)

custom_field_three
BROKEN PIPE
custom_field_two
1
customer
LACSD
datetime
2016-11-09T13:31:44-08:00