Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 9, 2016, 05:05 PM
  • 03 0263_03 0262_1192016_091637.mp4

Date
11/09/2016
W/O
0602283
Weather
Dry
Operator/Surveyor
DEVIN FRANKLIN
Sewer ID
Z00385
PipeID
P04865
Time
9:05 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7269
Sewer Name
03 MARKET STREET TRUNK
City
LONG_BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
07
Purpose
Routine Assessment
Project
20161104_DF_MARKET_STREET_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Upstream MH
03 0262
Downstream MH
03 0263
Dir. of Survey
Upstream
Length Surveyed
288.3 ft.
Total Length
288.3 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 03 0262 to 03 0263
MH: 03 0262MH: 03 0263upstream0 ft. AMH - Downstream Manhole, Survey Ends - 9:51 AM3.1 ft. MGO - General Observation - ROACHES THROUGHOUT THE REACH3.2 ft. MGO - General Observation - GREASE THROUGHOUT THE REACH31.6 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6", 6" - PROTRUDING 2 INCHES, CAPPED69.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - PROTRUDING 2 INCHES, OPEN125.4 ft. TFB - Tap Factory Made Abandoned, at 12 o'clock, -, within 8 inches of joint: YES, 6" - PROTRUDING 2 INCHES, OPEN173.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - OPEN193.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - POSSIBLE228.9 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 6", 6" - PROTRUDING 2 INCHES, OPEN236.2 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES288.3 ft. MWM - Water Mark, 10 %of cross sectional area288.3 ft. AMH - Upstream Manhole, Survey Begins - 9:08 AM288.3 ft. MWL - Water Level, 5 %of cross sectional area288.3 ft. MGO - General Observation - ROACHES @ MH

Observation photos (4)

  • Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - POSSIBLE

    95 ft. - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - POSSIBLE

  • Tap Factory Made Abandoned, at 12 o'clock, -, within 8 inches of joint: YES, 6" - PROTRUDING 2 INCHES, OPEN

    162.9 ft. - Tap Factory Made Abandoned, at 12 o'clock, -, within 8 inches of joint: YES, 6" - PROTRUDING 2 INCHES, OPEN

  • Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - PROTRUDING 2 INCHES, OPEN

    218.5 ft. - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - PROTRUDING 2 INCHES, OPEN

  • Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6", 6" - PROTRUDING 2 INCHES, CAPPED

    256.7 ft. - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6", 6" - PROTRUDING 2 INCHES, CAPPED

Observations (14)

DistanceCodeObservation
52.1CL
218.5TFPROTRUDING 2 INCHES, OPEN
256.7TFPROTRUDING 2 INCHES, CAPPED
114.4TFOPEN
95TFCPOSSIBLE
0MWM
288.3AMH9:51 AM
285.2MGOROACHES THROUGHOUT THE REACH
285.1MGOGREASE THROUGHOUT THE REACH
0AMH9:08 AM
0MWL
0MGOROACHES @ MH
59.4TBPROTRUDING 2 INCHES, OPEN
162.9TFBPROTRUDING 2 INCHES, OPEN

Properties (3)

custom_field_two
4
customer
LACSD
datetime
2016-11-09T09:05:54-08:00