Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 5, 2016, 01:37 PM
  • C 0661_C 0660_1152016_064323.mp4

Date
11/05/2016
W/O
0596966
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00266
PipeID
P23927
Time
6:37 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0335
Sewer Name
C JOINT OUTFALL C - UNIT 3F
City
SIGNAL HILL
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
01
Purpose
Routine Assessment
Project
20161104MDM_JOINT_OUTFALL_C_UNIT_3F
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
C 0661
Downstream MH
C 0660
Dir. of Survey
Downstream
Length Surveyed
329 ft.
Total Length
329 ft.
Structural Index
2
Structural Quick
3123
Structural Rating
9
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
9
Pipe schematic from manhole C 0661 to C 0660
MH: C 0661MH: C 0660downstream0 ft. AMH - Upstream Manhole, Survey Begins - 6:40AM0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped55.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped55.7 ft. MGO - General Observation - 18" VCP102.6 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - HAIRLINE103 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - H104 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped154.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped205.6 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - H205.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped254.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped302.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped325 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - SLIGHT329 ft. AMH - Downstream Manhole, Survey Ends - 7:00AM

Observation photos (1)

  • General Observation - 18" VCP

    55.7 ft. - General Observation - 18" VCP

Observations (16)

DistanceCodeObservation
325FCSLIGHT
55.7TFCCapped
0AMH6:40AM
55.7MGO18" VCP
0MWL
104TFCCapped
103FLH
329AMH7:00AM
205.6FCH
8TFCCapped
254.3TFCCapped
0MWM
154.3TFCCapped
302.4TFCCapped
102.6FCHAIRLINE
205.7TFCCapped

Properties (4)

custom_field_three
HAIRLINES 1 SLIGHT FRACTURE
custom_field_two
4
customer
LACSD
datetime
2016-11-05T06:37:35-07:00