Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 5, 2016, 01:05 PM
  • C 0662_C 0661_1152016_061621.mp4

Date
11/05/2016
W/O
0596966
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00266
PipeID
P23928
Time
6:05 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0335
Sewer Name
C JOINT OUTFALL C - UNIT 3F
City
SIGNAL HILL
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
01
Purpose
Routine Assessment
Project
20161104MDM_JOINT_OUTFALL_C_UNIT_3F
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
C 0661
Downstream MH
C 0662
Dir. of Survey
Upstream
Length Surveyed
330.6 ft.
Total Length
330.6 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
6
Pipe schematic from manhole C 0661 to C 0662
MH: C 0661MH: C 0662upstream0 ft. AMH - Upstream Manhole, Survey Ends - 6:30AM0.5 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. OPEN102.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open152.9 ft. MGO - General Observation - THIN SCALE BOTTOM OF PIPE168.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open202.7 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - HAIRLINE233.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped264 ft. MGO - General Observation - 18" VCP285.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped330.6 ft. AMH - Downstream Manhole, Survey Begins - 6:05AM330.6 ft. MWL - Water Level, 5 %of cross sectional area330.6 ft. MWM - Water Mark, 50 %of cross sectional area

Observation photos (2)

  • General Observation - 18" VCP

    66.6 ft. - General Observation - 18" VCP

  • General Observation - THIN SCALE BOTTOM OF PIPE

    177.7 ft. - General Observation - THIN SCALE BOTTOM OF PIPE

Observations (12)

DistanceCodeObservation
330.1MGOConn. @ Mh, 3 O' Clock. OPEN
0AMH6:05AM
0MWL
0MWM
127.9FCHAIRLINE
227.9TFCOpen
66.6MGO18" VCP
162.5TFOpen
45.2TFCCapped
97.4TFCCapped
330.6AMH6:30AM
177.7MGOTHIN SCALE BOTTOM OF PIPE

Properties (4)

custom_field_three
HAIRLINE
custom_field_two
4
customer
LACSD
datetime
2016-11-05T06:05:00-07:00