Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 3, 2016, 05:15 PM
  • 03 0278_03 0277_1132016_102434.mp4

Date
11/03/2016
W/O
0602283
Weather
Dry
Operator/Surveyor
IGNACIO
Sewer ID
Z00385
PipeID
P04882
Time
10:15 AM
Certificate
U-115-06022628
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7266
Sewer Name
03 MARKET STREET TRUNK
City
LONG BEACH
Loc. details
Alley
Location Code
H
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
07
Purpose
Routine Assessment
Project
20161103MI_MARKET_STREET_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
03 0278
Downstream MH
03 0277
Dir. of Survey
Downstream
Length Surveyed
414.9 ft.
Total Length
414.9 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2300
O&M Rating
6
Overall Index
2
Overall Quick
Overall Rating
6
Pipe schematic from manhole 03 0278 to 03 0277
MH: 03 0278MH: 03 0277downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 10:30AM8.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES37.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"41.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"87.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - Open91.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"140.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - Open144.3 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"189.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - Open192.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"243 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - Open247.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"287.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - Open291.3 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"341.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - Open345.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"390 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"394.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"414.9 ft. AMH - Downstream Manhole, Survey Ends - 10:57AM414.9 ft. MGO - General Observation - CONNECTION AT THE MH, 3 OCLOCK, ACTIVE.

Observation photos (1)

  • Downstream Manhole, Survey Ends - 10:57AM

    414.9 ft. - Downstream Manhole, Survey Ends - 10:57AM

Observations (22)

DistanceCodeObservation
287.4TFOpen
140.6TFOpen
243TFOpen
345.5TFC
341.7TFOpen
291.3TBC
247.5TFC
144.3TBC
192.9TFC
37.3TFA
8.1DAGS
394.1TFC
0MWM
390TFC
41.5TFC
414.9AMH10:57AM
0MWL
0AMH10:30AM
91.1TFC
414.9MGOCONNECTION AT THE MH, 3 OCLOCK, ACTIVE.
87.5TFOpen
189.6TFOpen

Properties (3)

custom_field_two
4
customer
LACSD
datetime
2016-11-03T10:15:36-07:00