Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 3, 2016, 10:26 AM
  • 02 1654_02 1653 _1132016_044546.mp4

Date
11/03/2016
W/O
597130
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00289
PipeID
P18809
Time
3:26 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0330
Sewer Name
02 MONTEREY PARK EXTENSION TRUNK
City
MONTEREY PARK
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
09
Purpose
Routine Assessment
Project
20161103MDM_MONTEREY_PARK_EXTENSION_TRUNK
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
02 1654
Downstream MH
02 1653
Dir. of Survey
Downstream
Length Surveyed
167.3 ft.
Total Length
167.3 ft.
Structural Index
3
Structural Quick
4326
Structural Rating
24
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
24
Pipe schematic from manhole 02 1654 to 02 1653
MH: 02 1654MH: 02 1653downstream0 ft. AMH - Upstream Manhole, Survey Begins - 4:40AM0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 6 O' Clock. Active6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE SEVERE AGG ATTACHED6 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG15.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - PEELING CONCRETE SEVERE AGG ATTACHED25 ft. MGO - General Observation - 15" NRCP33.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO38.1 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG38.7 ft. MGP - General Photograph - SHEET PEELING CONCRETE38.7 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES - MULTI LAYER PEELING CONCRETE68.2 ft. MGO - General Observation - 15" NRCP75.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - MULTI LAYER PEELING83.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - PEELING CONCRETE SEVERE AGG ATTACHED94 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open97.1 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG167 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - PEELING CONCRETE SEVERE AGG ATTACHED167 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG167.3 ft. AMH - Downstream Manhole, Survey Ends - 5:15AM

Observation photos (12)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE SEVERE AGG ATTACHED

    6 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE SEVERE AGG ATTACHED

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    6 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - PEELING CONCRETE SEVERE AGG ATTACHED

    15.9 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - PEELING CONCRETE SEVERE AGG ATTACHED

  • General Observation - 15" NRCP

    25 ft. - General Observation - 15" NRCP

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO

    33.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

    38.1 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • General Photograph - SHEET PEELING CONCRETE

    38.7 ft. - General Photograph - SHEET PEELING CONCRETE

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES - MULTI  LAYER PEELING CONCRETE

    38.7 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES - MULTI LAYER PEELING CONCRETE

  • General Observation - 15" NRCP

    68.2 ft. - General Observation - 15" NRCP

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - MULTI LAYER PEELING

    75.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - MULTI LAYER PEELING

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - PEELING CONCRETE SEVERE AGG ATTACHED

    83.9 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - PEELING CONCRETE SEVERE AGG ATTACHED

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

    97.1 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

Observations (20)

DistanceCodeObservation
6SSSPEELING CONCRETE SEVERE AGG ATTACHED
97.1SAMSEVERE AGG
33.1SSS
0AMH4:40AM
83.9SSSPEELING CONCRETE SEVERE AGG ATTACHED
0MWM
38.7MGPSHEET PEELING CONCRETE
15.9SSSPEELING CONCRETE SEVERE AGG ATTACHED
6SAMSEVERE AGG
75.1SSSMULTI LAYER PEELING
167.3AMH5:15AM
38.7SSSMULTI LAYER PEELING CONCRETE
25MGO15" NRCP
68.2MGO15" NRCP
0MWL
167SSSPEELING CONCRETE SEVERE AGG ATTACHED
38.1SAMSEVERE AGG
167SAMSEVERE AGG
94TFOpen
0MGOConn. @ Mh, 6 O' Clock. Active

Properties (4)

custom_field_three
DEEP PEELING CONCRETE SEVERE AGG ATTACHED
custom_field_two
1
customer
LACSD
datetime
2016-11-03T03:26:51-07:00