- Date
- 11/03/2016
- W/O
- 597130
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00289
- PipeID
- P18814
- Time
- 12:39 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- H0330
- Sewer Name
- 02 MONTEREY PARK EXTENSION TRUNK
- City
- MONTEREY PARK
- Loc. details
- Easement/Right of Way
- Location Code
- D
- Use of Sewer
- Sanitary Sewer
- District
- District 02
- Page No.
- 09
- Purpose
- Routine Assessment
- Project
- 20161103MDM_MONTEREY_PARK_EXTENSION_TRUNK
- Material
- NRCP
- Shape
- Circular
- Height
- 15 in.
- Upstream MH
- 02 1658
- Downstream MH
- 02 1657A
- Dir. of Survey
- Downstream
- Length Surveyed
- 110.7 ft.
- Total Length
- 110.7 ft.
- Structural Index
- 3
- Structural Quick
- 4131
- Structural Rating
- 11
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 11
Pipe schematic from manhole 02 1658 to 02 1657A Observation photos (5)

2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

8 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE SEVERE AGG ATTACHED

8 ft. - General Observation - 15" NRCP

8 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

99.5 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - PEELING CONCRETE SEVERE AGG ATTCHED