Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 4, 2016, 09:42 AM
Date
01/04/2016
W/O
0546885
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00158
PipeID
P10063
Time
1:42 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6667
Sewer Name
D JOINT OUTFALL D - UNIT 7
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
13
Purpose
Capital Improvement Program Assesment
Project
20160104MDM_JOINT_OUTFALL_D_UNIY_7
Material
RCP-CTL
Shape
Circular
Height
60 in.
Upstream MH
D 0125
Downstream MH
D 0124
Dir. of Survey
Downstream
Length Surveyed
673.5 ft.
Total Length
673.5 ft.
Structural Index
4
Structural Quick
5h4Z
Structural Rating
1730
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
1730
Pipe schematic from manhole D 0125 to D 0124
MH: D 0125MH: D 0124downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - MH CONN OPEN STOPLOG IN PLACE 3:000 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 2:25AM2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. MGO - General Observation - MISSING TILES 100% START 8:00 TO 4:002 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR2 ft. MGO - General Observation - MAG COAT 50% START2.2 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES - LONG REBAR7.5 ft. MGO - General Observation - MISSING TILES 30%18.3 ft. SAP - Surface Aggregate Projecting, from 12 to 04 o'clock, within 8 inches of joint: YES, Start20 ft. SRC - Surface Reinforcement Corroded, from 12 to 03 o'clock, within 8 inches of joint: YES - CORODDED BEYOUND REBAR25.5 ft. MGO - General Observation - MAG COAT 70% START25.5 ft. SRC - Surface Reinforcement Corroded, from 12 to 04 o'clock, within 8 inches of joint: NO - CIRCUM REBAR34.5 ft. SAP - Surface Aggregate Projecting, from 12 to 04 o'clock, within 8 inches of joint: YES, Finish - CIRCUM73.4 ft. MGO - General Observation - MISSING TILES 20%107.5 ft. SRC - Surface Reinforcement Corroded, from 12 to 02 o'clock, within 8 inches of joint: NO - CORRODED BEYOUND REBAR107.5 ft. MGP - General Photograph111.1 ft. SRC - Surface Reinforcement Corroded, from 12 to 03 o'clock, within 8 inches of joint: NO - CORRODED BEYOUND REBAR128 ft. MGO - General Observation - MISSING TILES 20%144.8 ft. MGO - General Observation - MISSING TILES 30%181.2 ft. MGO - General Observation - MISSING TILES 20%206 ft. MGO - General Observation - MISSING TILES 50%232.4 ft. SAP - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM236.3 ft. MGO - General Observation - MISSING TILES 20%262.4 ft. MGO - General Observation - MISSING TILES 20%285.8 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: NO302.2 ft. MGO - General Observation - MISSING TILES 20%320 ft. MGO - General Observation - MISSING TILES 20%359.8 ft. MGO - General Observation - MISSING TILES 30%378 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO382.2 ft. MGO - General Observation - MISSING TILES 20%434.9 ft. SRP - Surface Reinforcement Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM447.4 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CORRODED BEYOUND REBAR452.2 ft. MGP - General Photograph457 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - CORRODED BEYOUND REBAR461.6 ft. MGP - General Photograph469.7 ft. MGP - General Photograph521.5 ft. MGP - General Photograph568.4 ft. SRP - Surface Reinforcement Projecting, from 09 to 03 o'clock, within 8 inches of joint: NO - CIRCUM575.2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - REBAR MISSING-CORRODED BEYOUND REBAR582.1 ft. MGP - General Photograph633 ft. MGP - General Photograph658.9 ft. MGP - General Photograph673.1 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish673.1 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - REBAR MISSING-CORRODED BEYOUND REBAR673.1 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish673.1 ft. MGO - General Observation - MISSING TILES 100% FINISH673.1 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish673.1 ft. MGO - General Observation - MAG COAT 70% FINISH673.1 ft. SRP - Surface Reinforcement Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish673.5 ft. AMH - Downstream Manhole, Survey Ends - 3:25AM

Observation photos (39)

  • General Observation - MISSING TILES 100% START 8:00 TO 4:00

    2 ft. - General Observation - MISSING TILES 100% START 8:00 TO 4:00

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    2 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • General Observation - MAG COAT 50% START

    2 ft. - General Observation - MAG COAT 50% START

  • Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES - LONG REBAR

    2.2 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES - LONG REBAR

  • General Observation - MISSING TILES 30%

    7.5 ft. - General Observation - MISSING TILES 30%

  • Surface Aggregate Projecting, from 12 to 04 o'clock, within 8 inches of joint: YES, Start

    18.3 ft. - Surface Aggregate Projecting, from 12 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Corroded, from 12 to 03 o'clock, within 8 inches of joint: YES - CORODDED BEYOUND REBAR

    20 ft. - Surface Reinforcement Corroded, from 12 to 03 o'clock, within 8 inches of joint: YES - CORODDED BEYOUND REBAR

  • General Observation - MAG COAT 70% START

    25.5 ft. - General Observation - MAG COAT 70% START

  • Surface Reinforcement Corroded, from 12 to 04 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    25.5 ft. - Surface Reinforcement Corroded, from 12 to 04 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Aggregate Projecting, from 12 to 04 o'clock, within 8 inches of joint: YES, Finish - CIRCUM

    34.5 ft. - Surface Aggregate Projecting, from 12 to 04 o'clock, within 8 inches of joint: YES, Finish - CIRCUM

  • General Observation - MISSING TILES 20%

    73.4 ft. - General Observation - MISSING TILES 20%

  • Surface Reinforcement Corroded, from 12 to 02 o'clock, within 8 inches of joint: NO - CORRODED BEYOUND REBAR

    107.5 ft. - Surface Reinforcement Corroded, from 12 to 02 o'clock, within 8 inches of joint: NO - CORRODED BEYOUND REBAR

  • General Photograph

    107.5 ft. - General Photograph

  • Surface Reinforcement Corroded, from 12 to 03 o'clock, within 8 inches of joint: NO - CORRODED BEYOUND REBAR

    111.1 ft. - Surface Reinforcement Corroded, from 12 to 03 o'clock, within 8 inches of joint: NO - CORRODED BEYOUND REBAR

  • General Observation - MISSING TILES 20%

    128 ft. - General Observation - MISSING TILES 20%

  • General Observation - MISSING TILES 30%

    144.8 ft. - General Observation - MISSING TILES 30%

  • General Observation - MISSING TILES 20%

    181.2 ft. - General Observation - MISSING TILES 20%

  • General Observation - MISSING TILES 50%

    206 ft. - General Observation - MISSING TILES 50%

  • Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM

    232.4 ft. - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM

  • General Observation - MISSING TILES 20%

    236.3 ft. - General Observation - MISSING TILES 20%

  • General Observation - MISSING TILES 20%

    262.4 ft. - General Observation - MISSING TILES 20%

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: NO

    285.8 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: NO

  • General Observation - MISSING TILES 20%

    302.2 ft. - General Observation - MISSING TILES 20%

  • General Observation - MISSING TILES 20%

    320 ft. - General Observation - MISSING TILES 20%

  • General Observation - MISSING TILES 30%

    359.8 ft. - General Observation - MISSING TILES 30%

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO

    378 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO

  • General Observation - MISSING TILES 20%

    382.2 ft. - General Observation - MISSING TILES 20%

  • Surface Reinforcement Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM

    434.9 ft. - Surface Reinforcement Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CORRODED BEYOUND REBAR

    447.4 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CORRODED BEYOUND REBAR

  • General Photograph

    452.2 ft. - General Photograph

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - CORRODED BEYOUND REBAR

    457 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - CORRODED BEYOUND REBAR

  • General Photograph

    461.6 ft. - General Photograph

  • General Photograph

    469.7 ft. - General Photograph

  • General Photograph

    521.5 ft. - General Photograph

  • Surface Reinforcement Projecting, from 09 to 03 o'clock, within 8 inches of joint: NO - CIRCUM

    568.4 ft. - Surface Reinforcement Projecting, from 09 to 03 o'clock, within 8 inches of joint: NO - CIRCUM

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - REBAR MISSING-CORRODED BEYOUND REBAR

    575.2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - REBAR MISSING-CORRODED BEYOUND REBAR

  • General Photograph

    582.1 ft. - General Photograph

  • General Photograph

    633 ft. - General Photograph

  • General Photograph

    658.9 ft. - General Photograph

Observations (52)

DistanceCodeObservation
633MGP
232.4SAPCIRCUM
658.9MGP
0MWM
111.1SRCCORRODED BEYOUND REBAR
521.5MGP
378SRC
359.8MGOMISSING TILES 30%
0MGOMH CONN OPEN STOPLOG IN PLACE 3:00
73.4MGOMISSING TILES 20%
457SRCCORRODED BEYOUND REBAR
447.4SRCCORRODED BEYOUND REBAR
673.5AMH3:25AM
575.2SRCREBAR MISSING-CORRODED BEYOUND REBAR
34.5SAPCIRCUM
2SAMSEVERE AGG
107.5SRCCORRODED BEYOUND REBAR
128MGOMISSING TILES 20%
673.1SRC
181.2MGOMISSING TILES 20%
2.2SRCLONG REBAR
673.1SRCREBAR MISSING-CORRODED BEYOUND REBAR
582.1MGP
2MGOMISSING TILES 100% START 8:00 TO 4:00
2SRCCIRCUM REBAR
25.5MGOMAG COAT 70% START
452.2MGP
25.5SRCCIRCUM REBAR
206MGOMISSING TILES 50%
673.1SRC
673.1MGOMISSING TILES 100% FINISH
434.9SRPCIRCUM
320MGOMISSING TILES 20%
7.5MGOMISSING TILES 30%
382.2MGOMISSING TILES 20%
461.6MGP
0MWL
673.1SAM
568.4SRPCIRCUM
302.2MGOMISSING TILES 20%
18.3SAP
0AMH2:25AM
673.1MGOMAG COAT 70% FINISH
20SRCCORODDED BEYOUND REBAR
262.4MGOMISSING TILES 20%
673.1SRP
144.8MGOMISSING TILES 30%
2MGOMAG COAT 50% START
285.8SRC
107.5MGP
236.3MGOMISSING TILES 20%
469.7MGP

Properties (4)

custom_field_three
MISSING REBAR - CORRODED BEYOUND REBAR
custom_field_two
1
customer
LACSD
datetime
2016-01-04T01:42:24-08:00