Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 6, 2016, 04:48 PM
  • 02 1944A_02 1944_162016_090352.mp4

Date
01/06/2016
W/O
0547412
Weather
Light Rain
Operator/Surveyor
MIRANDA
Sewer ID
Z00246
PipeID
P04247
Time
8:48 AM
Certificate
U-1014-06022542
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7033
Sewer Name
02 DOUGLAS AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
08
Purpose
Routine Assessment
Project
20160106AM_DOUGLAS_AVENUE_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Upstream MH
02 1944A
Downstream MH
02 1944
Dir. of Survey
Downstream
Length Surveyed
269.8 ft.
Total Length
269.8 ft.
Structural Index
3
Structural Quick
4111
Structural Rating
5
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 02 1944A to 02 1944
MH: 02 1944AMH: 02 1944downstream0 ft. AMH - Upstream Manhole, Survey Begins - 9:02 AM0 ft. MGO - General Observation - ROACHES INSIDE THE MH.0 ft. MWM - Water Mark, 5 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONN. INSIDE THE MH. @ 06 O'CLOCK33.3 ft. CC - Crack Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES39.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"93.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"94.7 ft. MGO - General Observation - CHIPPING @ 09 O'CLOCK105.9 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"111.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"175.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"190.5 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - OPEN248 ft. FM - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES261.1 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: YES, 6" - OPEN267.6 ft. MGO - General Observation - SLIGHT GREASE/DEBRIS THROUGHOUT THE REACH267.9 ft. MGO - General Observation - ROACHES INSIDE THE MH.269.8 ft. AMH - Downstream Manhole, Survey Ends - 9:30 AM

Observation photos (1)

  • Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

    248 ft. - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

Observations (18)

DistanceCodeObservation
190.5TFOPEN
0AMH9:02 AM
0MGOROACHES INSIDE THE MH.
93.4TFA
0MWM
267.6MGOSLIGHT GREASE/DEBRIS THROUGHOUT THE REACH
33.3CC
94.7MGOCHIPPING @ 09 O'CLOCK
0MWL
111.1TFC
0MGOACTIVE CONN. INSIDE THE MH. @ 06 O'CLOCK
267.9MGOROACHES INSIDE THE MH.
261.1TFOPEN
175.9TFC
269.8AMH9:30 AM
39.8TFC
248FM
105.9TBA

Properties (3)

custom_field_two
4
customer
LACSD
datetime
2016-01-06T08:48:24-08:00