Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 4, 2016, 09:45 AM
Date
01/04/2016
W/O
0546885
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00158
PipeID
P23006
Time
1:45 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6667
Sewer Name
D JOINT OUTFALL D - UNIT 7
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
13
Purpose
Capital Improvement Program Assesment
Project
20160104MDM_JOINT_OUTFALL_D_UNIY_7
Material
RCP-CTL
Shape
Circular
Height
60 in.
Upstream MH
D JOINT
Downstream MH
D 0227
Dir. of Survey
Downstream
Length Surveyed
6.4 ft.
Total Length
6.4 ft.
Structural Index
5
Structural Quick
5442
Structural Rating
28
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
5
Overall Quick
Overall Rating
28
Pipe schematic from manhole D JOINT to D 0227
MH: D JOINTMH: D 0227downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:50AM0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MGO - General Observation - MH CONN ACTIVE 9:002 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - LONG REBAR2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR2 ft. MGO - General Observation - MAG COAT10% START2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. MGO - General Observation - MISSING TILES 90% START6.1 ft. MGO - General Observation - MISSING TILES 90% FINISH6.1 ft. MGO - General Observation - MAG COAT 10% FINISH6.1 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish6.1 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish6.1 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish6.4 ft. AMH - Downstream Manhole, Survey Ends - 5:05AM

Observation photos (4)

  • Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - LONG REBAR

    2 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - LONG REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • General Observation - MAG COAT10% START

    2 ft. - General Observation - MAG COAT10% START

  • General Observation - MISSING TILES 90% START

    2 ft. - General Observation - MISSING TILES 90% START

Observations (15)

DistanceCodeObservation
6.1MGOMISSING TILES 90% FINISH
2SRCLONG REBAR
0MWM
6.1MGOMAG COAT 10% FINISH
2SRCCIRCUM REBAR
0AMH4:50AM
2MGOMAG COAT10% START
6.1SAM
6.1SRC
6.4AMH5:05AM
0MWL
2SAMSEVERE AGG
6.1SRC
0MGOMH CONN ACTIVE 9:00
2MGOMISSING TILES 90% START

Properties (4)

custom_field_three
CORRODED REBAR
custom_field_two
2
customer
LACSD
datetime
2016-01-04T01:45:39-08:00